Siemens SIPART PS2 Series Operating Instructions Manual page 42

Electropneumatic positioners with 4 to 20 ma/hart
Hide thumbs Also See for SIPART PS2 Series:
Table of Contents

Advertisement

Installing/mounting
4.2 Mounting to linear actuator
4. If you use a short lever, the carrier pin is already pre-mounted. If you use the long lever
6DR4004-8L, fasten the carrier pin
Figure 4-3
Figure 4-4
5. Set the stroke value. The stroke value is specified on the nameplate of the actuator. Position
the pin center of the carrier pin
values on the lever scale matches the stroke value of the actuator, select the next higher
value on the scale.
For strokes ≥ 25 mm, select the scale (90). For strokes < 25 mm, select the scale (33).
6. Set the transmission ratio selector (Page 48) to the value of the selected scale.
7. If you need the value of actuator travel after initialization in mm: ensure that the configured
stroke value matches the value of the "3.YWAY" parameter.
8. Push the pre-installed lever
with socket cap screw
42
Short lever
Long lever 6DR4004-8L with mounted carrier pin
on the corresponding value of the scale. If none of the
up to the endstop on the positioner shaft. Fasten the lever
.
with the existing parts to the long lever.
and cylinder head screw
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents