5.2.4.2
In the basic unit with Analog Output Module (AOM) 6DR4004-6J/-8J (-Z D53)
You have a positioner with order suffix -Z order code D53. In this version of the positioner, the
current output of Analog Output Module (AOM) is electrically connected to the M12 connector.
Table 5-2
Current output terminal
61 (+)
Shield support of enclosure
62 (-)
5.2.4.3
In the basic unit with Position Transmitter (-Z D54)
You have a positioner with order suffix -Z order code D54. In this version of the positioner, the
installed Analog Input Module (AIM) 6DR4004-6F/-8F is electrically connected to the M12
connector. You connect the Position Transmitter 6DR4004-1ES/-2ES using the M12 connector.
Table 5-3
Terminal
REF
POS
GND
VCC
5.2.4.4
In the basic unit with Digital I/O Module (DIO) 6DR4004-6A/-8A (-Z D55)
You have a positioner with order suffix -Z order code D55. In this version of the positioner, the
current output of Digital I/O Module (DIO) is electrically connected to the M12 connector.
Table 5-4
Terminal of digital outputs A1 and A2
41 (+)
52 (-)
42 (-)
51 (+)
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE
Assignment diagram
Assignment diagram
Assignment diagram
Connection
5.2 Electrical wiring
Pole designation
1 - Brown
4 - Black
3 - Blue
Pole designation
2 - White
3 - Blue
4 - Black
1 - Brown
Pole designation
1 - Brown
4 - Black
3 - Blue
2 - White
89