System Data; High Elevation; Gas Line Installation; Pilot Adjustment - Regency Greenfire GF1500L Series Owners & Installation Manual

Hide thumbs Also See for Greenfire GF1500L Series:
Table of Contents

Advertisement

installation
GF1500LNG-1 SYSTEM DATA
Min. Supply Pressure
Low Setting Man.
Pressure
Max. Manifold
Pressure
Injector Size
(3.40 mm)
Minimum Input
Maximum Input
GF1500LLP-1 SYSTEM DATA
Min. Supply Pressure
Low Setting Man.
Pressure
Max. Manifold
Pressure
Injector Size
(1.99 mm)
Minimum Input
Maximum Input
GF1500LULPG-1 SYSTEM DATA
Min. Supply Pressure
Low Setting Man.
Pressure
Max. Manifold
Pressure
Injector Size
(1.85 mm)
Minimum Input
Maximum Input

HIGH ELEVATION

This unit is approved for altitude 0 to 1372m.
GAS LINE
INSTALLATION
Since some municipalities have additional local
codes it is always best to consult with your local
authorities.
When using copper or flex connectors use only
approved fittings. Always provide a union so
that gas lines can be easily disconnected for
servicing. Flare nuts for copper lines and flex
connectors are usually considered to meet this
requirement.
NOTE: A approved shutoff valve should be
supplied in or near the unit (or as per local
codes) for ease of servicing this appliance.
Access is required to the flex connection
where joined to copper.
32
|
Greenfield® G1500L Gas Fireplace

PILOT ADJUSTMENT

1.13 kPa
Periodically check the pilot flames. Correct flame
0.4 kPa
pattern has two strong blue flames: 1 flowing
around the flame sensor and 1 flowing across
the burner (it does not have to be touching the
0.87 kPa
burner).
Burner
#29 DMS
36.9 MJ/h
50 MJ/h
Note: If you have an incorrect flame pattern,
2.75 kPa
contact your Regency
1.6 kPa
instructions.
Incorrect flame pattern will have small, probably
2.49 kPa
yellow flames, not coming into proper contact
with the rear burner or flame sensor.
#47 DMS
GAS PIPE PRESSURE
TESTING
37.9 MJ/h
The appliance must be isolated from the gas sup-
49 MJ/h
ply piping system by closing its individual manual
shut-off valve during any pressure testing of the
gas supply piping system at test pressures equal
to or less than 3.45 kPa. Disconnect piping from
2.75 kPa
valve at pressures over 3.45kPa.
1.6 kPa
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
2.49 kPa
at the pressure test point.
#49 DMS
Note: To properly check gas pressure, both
inlet and manifold pressures should be
33.7 MJ/h
checked using the valve pressure ports
on the valve.
44 MJ/h
1. Make sure the unit is in the "OFF" position.
2. Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a suitable wide
flat screwdriver.
3. Attach manometer to "IN" and/or "OUT" pressure
tap(s) using a suitable ID hose.
4. Turn the unit on with the remote or manual
switch
5. The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified on the safety label.
NOTE: All the adjustments must be carried out in
the following order:
Remove the modulator plastic cap (A) using
needle nose pliers.
Maximum pressure: Turn the unit ON to its highest
input rating. Screw in the nut (B) to increase the
outlet pressure and screw it out to decrease it. Use
a 10 mm wrench.
Flame Sensor
Ignitor
Pilot
dealer for further
®
NOTE: Do not screw in nut too far. If no pressure
increases after two full terms, place manometer
on inlet test point on gas valve and check flow-
ing inlet pressure.
NOTE: The outlet pressure must be set to maxi-
mum 2.49 kPa for both Propane/ULPG and 0.87
kPa for NG.
Minimum pressure: Remove one of the cables co
nected to the electric modulator. While holding the
nut (B) with a wrench, screw in the screw (C) to
increase the pressure and screw it out to decrease
it. Use a screwdriver 6x1 blade.
After carrying out all adjustments, block the setting
screws with paint, taking care not to obstruct the
breather orifice of the pressure.
Put back the modulator plastic cap.
WARNING: To ensure the correct operation of the
modulator it is necessary that the plastic cap (A) is
returned to its original location.
NOTE: The outlet pressure must be set to
minimum 1.6 kPa. for both Propane/ULPG
and 0.4 kPa for NG.
B
6. Turn on gas supply and plug in power cord.
7. At the end of all setting and adjustment opera-
tions, check electrical installation and gas leaks.
8. Check operation of flame control.
9. Check for proper flame appearance and glow
on logs.
10. When finished reading manometer, turn off the
unit, disconnect the hose and tighten the screw
(clockwise) with a suitable flat screwdriver.
Note: Screw should be snug, but do not
over tighten.
Installer Notice:
These instructions must be left with
the appliance.