WARNING:
If the information in these instructions are not followed
exactly, a fire or explosion may result causing property
damage, personal injury or loss of life.
FOR YOUR SAFETY
Do not store or use petrol or other flammable vapors and
liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
919-670
GF1500LST
®
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
Owners &
Installation Manual
MODELS:
GF1500LST-NG
GF1500LST-LP
GF1500LST-ULPG
LISTINGS AND CODE APPROVALS
These gas appliances have been tested
in accordance with AS4553 / NZS5262
/ NZS5266 and have been certified by
IAPMO R&T Oceana for installation and
operation as described in these Installation
and Operating Instructions.
Must be installed as per AS/NZS 5601
Your unit should be serviced annually by
an authorised service person.
FOR YOUR SAFETY
What to do if you smell gas:
Do not try to light any appliance.
Do not touch any electrical switch.
Do not use any phone in your
building.
Immediately call your gas supplier
from a neighbour's phone. Follow
the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fire department.
December 8, 2016

Advertisement

Table of Contents
loading

Summary of Contents for Regency GF1500LST-NG

  • Page 1 Greenfire GF1500LST ® Owners & Gas Fireplace Installation Manual MODELS: GF1500LST-NG GF1500LST-LP GF1500LST-ULPG LISTINGS AND CODE APPROVALS These gas appliances have been tested in accordance with AS4553 / NZS5262 / NZS5266 and have been certified by IAPMO R&T Oceana for installation and operation as described in these Installation and Operating Instructions.
  • Page 2: Pairing The Remote Handset And Control Box Id Code

    Note: The pairing up process can be carried out by anyone. Note: In addition; please also go to: www.regency-fire.com.au "Care and Tip video" to see the pairing up video. Note: In an event of power failure when power is restored, the unit will initiate an automatic restart sequence if the remote is still indicating that the heater is on.
  • Page 3: Table Of Contents

    Unit Installation with Vertical Termination ....27 Parts Unit Installation ............28 High Elevation ..............29 Main Assembly ............50 Gas Line Installation ............29 Accessories ..............52 Pilot Adjustment ............29 Warranty Gas Pipe Pressure Testing ..........29 Wiring Diagram ............30 Warranty ..............54 845 S.I.T. Valve Description .........30 Regency GF1500LST Gas Fireplace...
  • Page 4: Copy Of Data Badge

    Oct. 3/16: Updated data + added approval # APPLIANCE WHILE IN OPERATION. DO NOT OPERATE WITH PANELS, COVERS OR GUARDS Oct. 19/16: Added Min. supply pressure REMOVED FROM THIS APPLIANCE. DO NOT ENCLOSE THIS APPLIANCE. DO NOT DO NOT MODIFY THIS APPLIANCE. 908-602a Regency GF1500LST Gas Fireplace...
  • Page 5: Unit Dimensions

    Dimension drawings shown without fascias NOTE: DUE TO NATURE AND DESIGN OF THE GF1500LST DOUBLE SIDED UNIT, SIDE A PROJECTS MORE HEAT THAN SIDE B ON THE UNIT. PLEASE NOTE THIS BEFORE COMMENCING THE INSTALLATION PROCESS. Regency GF1500LST Gas Fireplace...
  • Page 6: Important Message

    9. Wear gloves and safety glasses for protection while doing required maintenance. 10. Be aware of electrical wiring locations in walls and ceilings when cutting holes for termination. Regency GF1500LST Gas Fireplace...
  • Page 7: Installation Checklist

    Have an authorized inspector, dealer, or installer review your plans before installation. Note: For flue terminations refer to "Exterior Flue Termination Locations" section. Regency GF1500LST Gas Fireplace...
  • Page 8: Clearances

    If the television is left unprotected, Note: No hearth required the extreme heat being emitted from this appliance will result in damage to the television. See clearance requirements for mantle. Installed Close to Floor Installed close to ceiling. Alcove Regency GF1500LST Gas Fireplace...
  • Page 9: Mantel Clearances

    To Unit 702mm 702mm Top of Top of Top of Base Base Fireplace Fireplace Fireplace Opening Opening Opening MANTEL LEG CLEARANCES Combustible mantel leg clearances as per diagram: 295mm 219mm 203mm 146mm 203mm 146mm 219mm 295mm Regency GF1500LST Gas Fireplace...
  • Page 10: Unit Assembly Prior To Installation

    2. Easier access to gas connection with panel removed. 3. Install any optional components with access panel removed. 4. Reinstall access panel with 8 screws. Note: Access panel is no longer accessible once facing material installed. Installation Access Panel-Side B only. Regency GF1500LST Gas Fireplace...
  • Page 11: Framing Dimensions

    **Finished material thickness includes: non combustible material, tile slate, etc. A minimum thickness of 12mm non-combustible facing board compliant with AS1530-1 and AS1530- 3 is required. Timber studs (on edge) Finished Floor center of hole SIDE B SIDE A SIDE A Regency GF1500LST Gas Fireplace...
  • Page 12: Optional Framing Kit

    3. Install 3 top horizontal studs with 2 screws on each side. 4 QTY Horizontal Studs 2 QTY 2 QTY 2 QTY Vertical Side 516mm minus 2X fi nishing material Cross Center Horizontal studs are adjustable in 12mm increments. 07.13.16 919-679 Regency GF1500LST Gas Fireplace...
  • Page 13 5. Install 1(one) thin vertical studs on the left side of the unit as shown with 2(two)screws on each end. 7. Proceed with the installation of non-combustible and fi nishing materials. Side Support Thin Vertical Stud 919-679 07.13.16 Regency GF1500LST Gas Fireplace...
  • Page 14: Non Combustible Facing Installation

    The finishing of the walls surrounding Regency is as critical as the installation itself. The temperatures around damage to board. The non combustible board must be a mini- linear gas fireplaces are typically higher than would be acceptable for the mum of 12mm thick and comply with AS1530-1 and AS1530-3.
  • Page 15: Framing & Finishing

    The faceplate will not be able to be mounted if finished material is beyond 38mm. 1267mm Unit shown with inner door frame only Using the clean edge of the unit, shown in a typical tiled facing Regency GF1500LST Gas Fireplace...
  • Page 16: Combustible Requirements

    11 of the framing dimensions must the opening of the unit. be adhered to. For example., Unit raised 300mm then B + 300mm = 1311mm. Non-combustible Combustible material ( 241mm) (158mm) Regency GF1500LST Gas Fireplace...
  • Page 17: Exterior Flue Termination Locations

    EXTERIOR FLUE TERMINATION LOCATIONS FIGURE 6.2 (in part): LOCATION OF FLUE TERMINALS OF BALANCED FLUE AS/NZ 5601, ROOM-SEALED, FAN ASSISTED, OR OUTDOOR APPLIANCE Regency GF1500LST Gas Fireplace...
  • Page 18: Clearances

    3 See Figure J3 for clearances required from a flue terminal to an LP Gas cylinder. A flue terminal is considered to be a source of ignition. 4 For appliance not addressed above acceptance should be obtained from the Technical Regulator. 5 Minimum clearance d and e also apply to any combustion air intake openings of appliances. Regency GF1500LST Gas Fireplace...
  • Page 19: Flue Restrictor Settings

    5. Once the flue restrictor plate is in the required position, secure with Screw Positions screws. 6. Reassemble unit by reversing Steps 3-1. Set 2 - 35mm SET 2 Screw Positions Set 3 - 25mm SET 3 Regency GF1500LST Gas Fireplace...
  • Page 20: Flueing Arrangements

    S.S. screws #8 x 38mm drill point Notes: 1) Liner sections should be continuous without any joints or seams. 2) Only Flex pipe purchased from Regency may be ® used for Flex installations 3) Horizontal flue must be supported every 0.9m.
  • Page 21: Rigid Pipe Flueing Systems

    Do not combine flueing components from different venting systems. Exception: However, use of the the AstroCap is acceptable with all systems. When using Rigid Flue other than Simpson Dura-Vent, 3 screws must be used to secure rigid pipe to unit. Regency GF1500LST Gas Fireplace...
  • Page 22: Flueing Introduction

    A flue guard should be used whenever the termination is lower than the specified minimum or as per local codes. • Flex system can only be used up to 3m - otherwise rigid system must be used. Regency GF1500LST Gas Fireplace...
  • Page 23: Horizontal Venting With Two (2) 90 Elbows

    2. Only Flex pipe purchased from FPI may be used for Flex installations. 3. Horizontal flue must be supported every 0.9 m. 4. A wall thimble is mandatory for all horizontal terminations due to high temperatures. Regency GF1500LST Gas Fireplace...
  • Page 24: Direct Flue Zero Clearance Top Exit Vertical Flue Kit Installation Instructions Gf1500Lst

    Milpac Milpac NOTE: USE A MINIMUM OF 3 SCREWS EQUIDISTANT TO SECURE EVERY INNER FLUE PIPE JOINT AS WELL Mill-Pac SEALANT AS MILL-PAC SEALANT INNER FLUE Regency GF1500LST Gas Fireplace...
  • Page 25: Venting Arrangements

    Set 2 or Set 3, if required. Note: Must use optional flue adaptor when using Duravent Rigid Pipe (Part # 770-994). Max. 3m (centerline to centerline) Regency GF1500LST Gas Fireplace...
  • Page 26: Unit Installation With Horizontal Termination

    "THIS UNIT MUST ALWAYS all local and national building codes, and TERMINATE / FLUE must not be blocked or obstructed. See "Exterior Flue Termination Locations" DIRECTLY TO THE section for more details. OUTDOORS." NOTE: "NOT INTENDED FOR FIREPLACE INSERT". Regency GF1500LST Gas Fireplace...
  • Page 27: Unit Installation With Vertical Termination

    Flue Height clearances . (Minimum600mm) As Per AS/NZS 5601-2013 4. Assemble the desired lengths of pipe and elbows. Ensure that all pipes and elbow con- nections are in the fully twist-locked position and sealed. Diagram 5 Regency GF1500LST Gas Fireplace...
  • Page 28: Unit Installation

    51mm X 102mm x 51mm x 152mm dia. flue pipe AstroCap XL with spring spacer Termination Cap 8" (203) dia. air intake Screws "THIS UNIT MUST ALWAYS Wall Thimble* TERMINATE / FLUE Screws *Mandatory on all DIRECTLY TO THE OUTDOORS." horizontal terminations. Regency GF1500LST Gas Fireplace...
  • Page 29: High Elevation

    NOTE: Do not screw in nut too far. If no pressure PILOT ADJUSTMENT GF1500LST-NG SYSTEM DATA increases after two full terms, place manometer on inlet test point on gas valve and check flow- Min. Supply Pressure 1.13 kpa Periodically check the pilot flames. Correct flame ing inlet pressure.
  • Page 30: Wiring Diagram

    ULPG Full Open Outlet Pressure Note: Any damage due to carboning resulting 7. Gas Outlet Pressure Electric Modulator from improperly setting the aeration 8. Pilot Outlet controls is NOT covered under warranty. 9. Main Gas Outlet Regency GF1500LST Gas Fireplace...
  • Page 31: Conversion Kit From Ng To Lp/Ulpg

    8. Remove burner orifi ce with a 12mm spanner and discard. Use an- other spanner to hold on to the elbow below the orifi ce. Diagram 1 - Burner Side Panels Diagram 5- Remove Burner Ori ce 10.04.16 919-722 Regency GF1500LST Gas Fireplace...
  • Page 32 19. At the end of all setting and adjustment operations, check electri- cal installation and gas leaks. 20. Check operation of fl ame control. 21. Check for proper fl ame appearance and glow on logs. Installer Notice: These instructions must be left with the appliance. 919-722 10.04.16 Regency GF1500LST Gas Fireplace...
  • Page 33: Optional Fan Ducting Kit Installation

    Wall Adapter Plate NOTE: The fan kit (946-591) does not contain any ducting. The optional extension duct kit (7 in the noted table) is 4.5 metres in length and its part number is 946-596. 919-725 12.Oct. 2016 Regency GF1500LST Gas Fireplace...
  • Page 34: Optional Fan Kit Installation

    fi tted. 5. Wire up the the fan, wall switch and power supply per local codes. See wiring diagram as reference. *Electrician to supply wiring. 6. Screw fan junction box to the fan housing. 919-725 12.Oct. 2016 Regency GF1500LST Gas Fireplace...
  • Page 35 Alternate Switches: May use the following. Check with local authorities and electrician. Green CLIPSAL 203 2E45 OUD - Dimmer CLIPSAL 2031 VF3CSF - 3 Speed Note: When using on/off switch (supplied) or dimmer remove red wire at motor ( not used) 919-725 12.Oct. 2016 Regency GF1500LST Gas Fireplace...
  • Page 36: Log Set Installation

    2. Facing Side A—position Log 2 on the right side of the Log 1. There are 2 + 3 as shown in Diagram 4. landing spots on the burner to rest Log 2 into, lean the top portion of Log 2 on Log 1. Diagram 4 Diagram 2 919-720 10.04.16 Regency GF1500LST Gas Fireplace...
  • Page 37 7. Line up the pin locator on Log 7 onto the pin on Log 6. The opposite end of Log 7 has a landing spot on the burner as shown in Diagram 8. Diagram 11 Diagram 8 Diagram 12 - Side B completed (embers are circled) 919-720 10.04.16 Regency GF1500LST Gas Fireplace...
  • Page 38: Front Trim Removal / Installation

    1. Remove front trim piece - see instructions above. 2. Remove two (2) screws in locations shown below to release panel clips. Panel Clip 3. Remove panels by sliding out. Panel Clip Screw Locations 4. Reverse steps to reinstall. Regency GF1500LST Gas Fireplace...
  • Page 39: Faceplate And Deflector Installation

    Deflector on opposite side. WARNING: Turn off the unit by way of the wall switch or remote. Allow unit to cool at least 10 min. - prior to remov- Diagram 3 ing the faceplate. 919-593b 07.18.16 Regency GF1500LST Gas Fireplace...
  • Page 40: Screen & Inner Door Frame Installation

    2. Bend Tab on Screen Mesh to 90º as shown in Diagram 2. Secure to Inner Door Frame with one (1) screw as shown in Diagram 2a. Diagram 3 4. Repeat on opposite side. Diagram 2 Diagram 2a Regency GF1500LST Gas Fireplace...
  • Page 41: Optional Finishing Trim Installation

    1. Install the optional finishing trim by lining up trim with the outside of the fascia. Press trim inward firmly to seat onto the unit. Finishing Trim Installed 2. Pull trim outward–away from the unit to remove. Regency GF1500LST Gas Fireplace...
  • Page 42: Operating Instructions Operating Instructions

    FAN 1 speed to the next fan speed on adjacent isolation switch. e.g. LOW-MED-HIGH Use the Regency Remote Control Kit supplied 2. There is a black, manual, ON/OFF button located with this unit. Use of other systems may void Pressing and releasing the FAN 2 button will in the bottom left-hand corner of the unit.
  • Page 43: Copy Of Lighting Plate Instructions

    Fan: damage. Refer to the owner’s information Regency gas appliances use high tech fans to 1. Turn the unit ON by either the remote handset manual provided with this appliance. For push heated air farther into the room. It is not...
  • Page 44: Fan Service

    4. Remove burner by removing 2 screws in locations shown below in Diagram 2. Diagram 2 - Burner Screw Locations 5. Remove end panels—see instructions in this manual. 6. Remove 11 screws to remove fan access panels as shown in Diagram 3. tooltip Regency GF1500LST Gas Fireplace...
  • Page 45: Maintenance Instructions

    3. The faceplate is finished in a heat resistant CAUTION & WARNINGS: sealant. paint and should only be refinished with heat resistant paint. Regency® uses StoveBright * Do not clean when the glass is hot. 3. Check for evidences of excessive conden- Paint - Metallic Black 938-110.
  • Page 46: Troubleshooting

    Install log set as per Owners' Manual Fan operates but no ignition sequence Unit ignition pack gone into lockout Reset ignition pack by depressing black reset (no spark) button while unit controls are in the "ON" position (fan running) Regency GF1500LST Gas Fireplace...
  • Page 47: Glass Door Installation

    6. Pull the bottom of the door towards you until the door is angled away from the firebox by about 30°. Lift the door up and over the upper door hooks. 7. To install the glass door- reverse steps. Regency GF1500LST Gas Fireplace...
  • Page 48: Valve Tray Replacement

    4. Remove burner by removing 2 screws in locations shown below. 8. Replace with new valve tray. Diagram 2 - Burner Screw Locations 9. Reverse steps 6 through 1 to reinstall new valve tray. 5. Slide burner to the left and lift out. Regency GF1500LST Gas Fireplace...
  • Page 49: Electronic Components Parts List

    911-121 Ignition Module (2) 910-514 Jumper Wire         910-935 Manual Control Switch     **Note: The Control Box Cable wires for the FG38 come separately: 910-502, 910-505, 910-506, 910-507, 910-509 Regency GF1500LST Gas Fireplace...
  • Page 50: Parts List

    396-042F Plate Slide & Door Frame Tool 936-157 Gasket Tadpole Tape Alum F.Core ( sold per 25.4 mm, 629 mm required) 904-691 Glass U clips (Each) 696-930 Log Set - Complete 316-089F Nailing Strip - Bottom Regency GF1500LST Gas Fireplace...
  • Page 51 PARTS LIST MAIN ASSEMBLY SIDE A SIDE B Regency GF1500LST Gas Fireplace...
  • Page 52: Accessories

    Inner door frame - Stainless w/ Screen 33 606-544 Door Frame Overlay - Black 34 606-938 Fascia and Door Frame Black w/Screen 606-936 Fascia and Door Frame Stainless Steel w/Screen 606-951 Fascia Black Glass (not shown) Regency GF1500LST Gas Fireplace...
  • Page 53 NOTES notes Regency GF1500LST Gas Fireplace...
  • Page 54: Warranty Warranty

    FPI Fireplace Products International Ltd. (“the manufacturer”) through its wholly owned subsidiary, Fireplace Products Australia Pty Ltd (for Australia and New Zealand customers) and sold under the Regency® brand of fireplace products (collectively referred to herein as “FPI”), extends this Limited Lifetime Warranty to the original purchaser of this appliance provided the product remains in the original place of installation.
  • Page 55 Limited Lifetime Warranty. Revision Date: December 2016 Regency Gas Products Warranty Regency GF1500LST Gas Fireplace...
  • Page 56 FPI may void this warranty. INCORRECT INSTALLATION OR GAS PRESSURE SETTINGS ARE NOT COVERED BY WARRANTY. A SERVICE OR CALLOUT FEE WILL BE CHARGED IN THESE CIRCUMSTANCES. Revision Date: December 2016 Regency Gas Products Warranty Regency GF1500LST Gas Fireplace...
  • Page 57 (including negligence), statute or otherwise. (b) Loss means any expense, cost or damage of any kind and includes Consequential Loss and a fine or penalty imposed by a statutory or other authority. Revision Date: December 2016 Regency Gas Products Warranty Regency GF1500LST Gas Fireplace...
  • Page 58 Product Registration and Customer Support: Thank you for choosing a Regency Fireplace. Regency strives to be a world leader in the design, manufacture, and marketing of hearth products. To provide the best support for your product, we request that you complete a product registration form at http://www.regency-fire.com.au/Customer-Care/Warranty-Registration.aspx...
  • Page 59 Product Registration and Customer Support: Thank you for choosing a Regency Fireplace. Regency strives to be a world leader in the design, manufacture, and marketing of hearth products. To provide the best support for your product, we request that you complete a product registration form found on our Web Site under Customer Care within ninety (90) days of purchase.
  • Page 61 NOTES notes Regency GF1500LST Gas Fireplace...
  • Page 62 NOTES Regency GF1500LST Gas Fireplace...
  • Page 64 Installer: Please complete the following information Dealer Name & Address: ______________________________________________ ___________________________________________________________________ Installer: ___________________________________________________________ Phone #: ___________________________________________________________ Date Installed: ______________________________________________________ Serial No.: __________________________________________________________ Regency is a registered trademarks of FPI Fireplace Products International Ltd. © Copyright 2016, FPI Fireplace Products International Ltd. All rights reserved.