installation

CLEARANCES

Ref.
a
Below eaves, balconies and other projections:
Appliances up to 50 MJ/h input
Appliances up to 50 MJ/h input
b
From the ground, above a balcony or other surface*
c
From a return wall or external corner*
d
From a gas meter (M) (see Note 5)
(see Clause 5.11, 5.9 for vent terminal location of regulator)
(see Table 6.7 for New Zealand requirements)
e
From an electricity meter or fuse box (P)
f
From a drain or soil pipe
g
Horizontally from any building structure* or obstruction facing a terminal
h
From any other flue terminal, cowl, or combustion air intake
j
Horizontally from an openable window, door, non-mechanical air inlet, or any other opening into a building iwth
the exception of sub-floor ventilation:
Appliances up to 150MJ/h input*
Appliances over 150MJ/h input up to 200 MJ/h input*
Appliances over 200MJ/h inputup to 250 MJ/h input**
Appliances over 250MJ/h input*
All fan-assisted flue appliances, in the direction of discharge
k
From a mechanical air inlet, including a spa blower
n
Vertically below an openable window, non-mechanical air inlet, or any other opening into a building iwth the
exception of sub-floor ventilation:
Space heaters up to 50MJ/h input
Other appliances up to 50 MJ/h input
Appliance over 50 MJ/h input and up to 150 MJ/h input
Appliances over 150 MJ/h input
* Unless appliance is certified for closer installation.
† Prohibited area below electricity meter or fuse box extends to ground level.
NOTES:
1 Where dimension c, j or k cannot be achieved an equivalent horizontal distance measured diagonally from the
nearest discharge point of the terminal to the opening may be deemed by the Technical Regulator to comply.
2 See Clause 6. 9. 4 for restriction on the flue terminal under a covered area.
3 See Figure J3 for clearances required from a flue terminal to a propane gas cylinder. A flue terminal is con-
sidered to be a source of ignition.
4 For appliance not addressed above acceptance should be otained from the Technical Regulator.
5 Minimum clearance d and e also apply to any combustion air intake openings of appliances.
22
|
Greenfield® G1500L Gas Fireplace
Item
(see Note 5)
Minimum clearances (mm)
Natural
Fan
Draught
Assisted
300
200
500
300
300
300
500
300
1000
1000
500
500
150
75
500
500
500
300
500
300
1500
300
1500
500
1500
1500
-
1500
1500
1000
150
150
500
500
1000
1000
1500
1500