Flueing Arrangements; Horizontal Termination (Flex) - Regency Greenfire GF1500L Series Owners & Installation Manual

Hide thumbs Also See for Greenfire GF1500L Series:
Table of Contents

Advertisement

FLUEING ARRANGEMENTS

HORIZONTAL TERMINATION (FLEX)

Regency
Direct Vent System
®
These flueing systems, in combination with GF1500L, have been tested and listed as a Direct Vent system by AGA. The location of the termination cap must
conform to the requirements in the Flue Terminal Locations diagram from the "Exterior Flue Termination Locations" section.
FPI Direct Vent (Flex) System Termination Kits include all the
parts needed to install the GF1500L using a flexible vent.
FPI Kit #
Length Contains:
1)
#946-615
1.2 m
2)
3)
4)
#946-618
1.8 m
5)
6)
7)
#946-616
3 m
8)
9)
127mm dia. flue pipe
203mm dia.
203mm flexible liner (Kit length)
127mm flexible liner (Kit length)
spring spacers
thimble
AstroCap termination cap
screws
tube of Mill Pac
plated screws
S.S. screws #8 x 38mm drill point
Wall Thimble
(Mandatory in all
Horizontal Terminations)
Flue pipe
AstroCap XL
Termination Cap
(Part #946-623/P)
spring spacer
Notes:
1) Liner sections should be continuous without any joints
or seams.
2) Only Flex pipe purchased from FPI may be used for Flex
installations.
3) Horizontal flue must be supported every 0.9m.
4) A wall thimble is mandatory for all horizontal terminations
due to high temperatures.
installation
Flue Guard - if required *
(Part #946-506/P)
TM
Greenfield® G1500L Gas Fireplace
|
25