Using the STARTER Control Panel (Motor Rotates)
Table 4-1
Signal (control
panel)
ON/OFF1
ON/OFF2
ON/OFF3
Pulse enable
Enable ramp-
function gener-
ator
Start/stop
ramp-function
generator
Enable
setpoint
Fig. 4-6
5. As shown in Fig. 4-6, click the Enables field to set the commands for enabling
the control words in the drive system.
Fig. 4-7
6. Choose Infeed control priority. The infeed (active line module) is switched on.
4-54
Control word sequence control
PROFIdrive
bit no. in CTW se-
quence control
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Click the Enables field.
Enables
Infeed control priority
SINAMICS S120 Getting Started with the STARTER Commissioning Tool – 04.2004 Edition
Meaning
0 = OFF (OFF1), stop via ramp-function generator,
followed by pulse block
1 = ON, operating condition
0 = Coast down (OFF2), pulse block, motor coasts
to standstill
1 = Do not coast down, operating condition
0 = Emergency stop (OFF3)
1 = No emergency stop, operating condition
0 = Disable operation, pulse block
1 = Enable operation, enable pulses
0 = Set ramp-function generator to 0
1 = Enable ramp-function generator
0 = Freeze ramp-function generator, retain cur-
rent output value
1 = Restart ramp-function generator, follows the
input value
1 = Enable setpoint
0 = Block setpoint and set to 0
Choose Infeed control
priority.