CHAPTER 12 External Interfaces

12.1 UPS Control Interface

Overview The UPS control interface is used to perform temporary data saving processing. In this processing, a
Connecting interfaces
146
reserved interruption for software occurs when the uninterruptible power supply (UPS) is used to
backup a power failure in the commercial AC power supply. In addition to this type of UPS control
interface, there are several other UPS units that use the general-purpose interface such as RS232C.
The configurations and definitions of the signal lines to be connected to the UPS system are shown
below. Do not use pin numbers unspecified below to connect to the UPS system.
Table 12.1
Signal
Definitions
names
BPS
Signal indicating faulty UPS
conditions
BTL
Signal indicating that the UPS
battery level has lowered and
that ineffectual battery char
ge may result after a certain
period of time (*1)
UPSON
Signal indicating the UPS is
operating
ACOFF
Signal notifying power failure
in the commercial AC supply
connected to the UPS (*2)
SG
System ground signal
ER (*4)
Signal indicating the main
cabinet is operating (*3)
ON indicates contacts are closed.
OFF indicates contacts are open.
*1
The normal power supply should be maintained by the UPS battery for at least 10 to
60 seconds after the connecting interface signal is turned on.
*2
For momentary power supply interruption of the commercial AC power not
exceeding two seconds, the normal battery power supply without activating ACOFF*
is recommended.
*3
This connecting interface signal identifies the status of the main cabinet to prevent
supplying battery power in case the signal is in the OFF (LOW) state (the main
cabinet is stopped), even though a power failure is detected by the UPS.
*4
ER signal may be left unused.
Definitions of UPS Signal Lines
Pin
Nos.
6
Enabled with ON.
7
Enabled with ON.
8
9
When power fails: ON
When power is normal:
OFF
5
1
Remarks