Commissioning At The Sinamics G120P Inverter Using The Iop - Siemens SIMOTICS FD 1LL1 Operating Instructions Manual

Induction motor
Table of Contents

Advertisement

7.9.3

Commissioning at the SINAMICS G120P inverter using the IOP

The SINAMICS G120P provides the IOP (Intelligent Operator Panel) located in the enclosure
door for operating, monitoring, and commissioning tasks. It can be used to set the motor
parameters.
1. Select the "basic commissioning" wizard. Only so can you enter unusual frequencies, such
2. Select "speed control" as control type.
3. Select "SIMOTICS FD" as motor type. This sets specific motor parameters for optimizing
4. Enter the performance plate data.
SIMOTICS FD 1LL1
Operating Instructions 04/2016
as 50.39 Hz or 100 Hz.
the operating behavior.
– Motor voltage
– Motor current
– Rated power
– Rated power factor cos φ
– Motor speed
The optimized pulse patterns are activated automatically once the "SIMOTICS FD" motor
type is selected (p300=14).
7.9 Setting the motor parameters at the converter
Start-up
103