Start-up

7.5 Setpoint values for monitoring the bearing temperature

7.4

Setting the automatic regreasing system

The relubrication is performed depending on the external voltage present at the regreasing
system.
● Prior to commissioning, set the time interval and the relubrication quantity at the automatic
● Observe the operating instructions for the regreasing system for its operation and the
See also
Interlock circuit for the automatic regreasing system (option) (Page 31)
7.5
Setpoint values for monitoring the bearing temperature
Prior to commissioning
If the machine is equipped with bearing thermometers, set the temperature value for
disconnection on the monitoring equipment before the first machine run.
Table 7-1
Set value
Alarm
Shutting down
Normal operation
Measure the normal operating temperature of the bearings T
°C. Set the values for shutdown and warning corresponding to the operating temperature T
Table 7-2
Set value
Alarm
Shutting down
94
regreasing system.
replacement of the grease cartridges.
Set values for monitoring the bearing temperatures before commissioning
Set values for monitoring the bearing temperatures
Temperature
115 °C
120 °C
at the installation location in
op
Temperature
T
+ 5 K ≤ 115 °C
operation
T
+ 10 K ≤ 120 °C
operation
SIMOTICS FD 1LL1
Operating Instructions 04/2016
.
op