Electrical connection
6.4 Connection
4. Make sure the terminal clamps
5. If you have loosened the terminal body clamping bolts
82
Insert the cable into the terminal clamps. Tighten the clamping nuts
torque as specified in the following table.
Terminal box
GT640 / 1XB1621 / 1XB1631 / 1XB1634
1XB7730 / 1XB7731
1XB7740 / 1XB7750
Image 6-9
Connection using terminal clamps (schematic diagram)
following torque:
Terminal box
1XB1621 / 1XB1631 / 1XB1634
GT640 / 1XB7730 / 1XB7731 /
1XB7740 / 1XB7750
For terminal boxes GT640, 1XB7730 and 1XB7731, the terminal element
using a terminal nut M12 on the threaded stud of the terminal support with a torque of 20 Nm.
,
are arranged correctly for the size of the conductor.
Tightening torque
8 Nm
4 Nm
8 Nm
Tightening torque
40 Nm
20 Nm
to the tightening
, then retighten them with the
SIMOTICS FD 1LL1
Operating Instructions 04/2016