Commissioning At The Sinamics G120P Inverter Using The Iop - Siemens SIMOTICS FD 1LH1 Operating Instructions & Installation Instructions

Low-voltage motor
Hide thumbs Also See for SIMOTICS FD 1LH1:
Table of Contents

Advertisement

Start-up
7.10 Setting the motor parameters at the converter
7.10.3

Commissioning at the SINAMICS G120P inverter using the IOP

The SINAMICS G120P provides the IOP (Intelligent Operator Panel) located in the enclosure
door for operating, monitoring, and commissioning tasks. It can be used to set the motor
parameters.
1. Select the "basic commissioning" wizard. Only so can you enter unusual frequencies, such
2. Select "speed control" as control type.
3. Select "SIMOTICS FD" as motor type. This sets specific motor parameters for optimizing
4. Enter the performance plate data.
110
as 50.39 Hz or 100 Hz.
the operating behavior.
– Motor voltage
– Motor current
– Rated power
– Rated power factor cos φ
– Motor speed
The optimized pulse patterns are activated automatically once the "SIMOTICS FD" motor
type is selected (p300=14).
SIMOTICS FD 1LH1
Operating Instructions 01/2019

Advertisement

Table of Contents
loading

Table of Contents