Group Assignment; Group Disablement Input; Operation; Peripherals - Bosch Radionics D8024 Operation And Installation Manual

Fire alarm control panel
Hide thumbs Also See for Radionics D8024:
Table of Contents

Advertisement

D8024/D10024A
Programming
The group disable function is for use by Trained Personnel only.

Group Assignment

Each detector or input device that is to be disabled must be assigned to a specific group using the Group
command in the Change Device options. The input device that will initiate the group disablement must also
be assigned to the same group. Press '7' to select the group option.

Group Disablement Input

The input device to be used to control the group disablement must have its 'Action' set to Group-Disable.
ONLY one input device must be assigned to act as the Group Disable input for a specific group.

Operation

When the input device is activated, the detectors and input devices within the specified group will be
disabled. The LCD on the panel will indicate there are 'xxx Inputs Disabled' where, 'xxx' is the number of
devices.
The Point Bypassed LED will illuminate to indicate that devices are disabled. If all the devices in a zone are
disabled, then the relevant zone LED will also be illuminated. The internal buzzer of the panel will not sound.
When the input device is returned to normal, the group disablement will be canceled.
If the initiating input device is assigned to the same zone as the group-disable devices, then the
Zone LED will not illuminate. The input device itself cannot be disabled and hence, not all devices in
the zone will be disabled.
To disable the initiating input device, use the Disable Device function in the panel.
At least one Pull Station MUST be located in the area covered by the disabled devices to provide a
means of manually indicating the presence of a fire.
5.6

Peripherals

All panels have the facility to drive various Input and Output devices on the 485 peripheral bus (the left hand
serial port D on all base cards).
Select the configure option
from Page 1 of the
Commissioning menus.
All panels have the facility to drive various Input and Output devices on the 485 peripheral bus (the left hand
serial port D on all base cards).
Select the configure option
from Page 1 of the
Commissioning menus.
Press '6' to select the 'Peripherals' option.
The display will present a list
of options for you to choose
from as follows:
The top left hand corner of the display reminds you that you are in configuration mode and shows that it is
the peripheral bus that is being examined. Press the appropriate number to select the required menu option.
5.6.1

Auto Learn

This facility saves considerable time and effort when installing a system, or when changing the units
connected to the peripheral bus. It allows the system to learn for itself what devices have been installed on
the peripheral bus.
50616B
D8024/D10024A Operation and Installation Guide
Page 26