D8024/D10024A
Installation
3.1.2
Alphanumeric/Interactive Control Keys
0
A
Shift
N
Key Legend
0 to 9
>
<
Change
Enter
No
Yes
Shift
•
The control keys are disabled at USER LEVEL 1. Pressing the SHIFT key will cause the display to prompt
for entry of the Level 2 password. The password must be entered to re-enable the control keys at Level 2.
3.1.3
System Control LED Indications
•
The Level 1 LED
Indicators are divided into
two sections.
•
The upper array of LED
Indicators shows the
operational conditional of
the panel and the
installation.
•
The lower array of Zone
LED Indicators shows the
location of a fire alarm or
trouble.
•
The standard Zone LED Indicators provide identification for up to 20 zones. On the D10024A panel, this can
be extended by adding either a further 20 zones (to give a total of 40 zones) or a further 60 zones (to give a
total of 80 zones).
•
The LED Indicators illuminate as red, yellow or green to give a clear indication of the panel status as follows:
Indicator
Blank
ALARM
System Trouble
Trouble Silenced
Point Bypassed
50616B
1
2
3
4
5
6
B
C
D
E
F
G
O
P
Q
R
S
T
Figure 3: Alphanumeric and Interactive Control Keys
Function
Press to enter numbers 0-9 or letters A-Z
Press to scroll through fire alarms or troubles manually on the display
Press to scroll back through fire alarms or troubles manually on the display
Press to change a display option (where allowed)
Press to confirm entry of a multiple digit number
Press to answer No, or terminate a display option
Press to answer Yes, or step through a display option
Press to show user options on the display
Press, during programming, to allow entry of Letters N-Z
Table 5: Alphanumeric and Interactive Control Keys
Color
Function
Red
The panel has detected a fire
alarm condition, or the 'Fire
Drill' key has been pressed.
Yellow
A trouble has been detected by the
panel.
Yellow
A trouble has been acknowledged
and the internal buzzer silenced.
Yellow
Part of the system, either input or
output, has been disabled manually
by the user.
D8024/D10024A Operation and Installation Guide
7
8
9
>
<
Change
H
I
J
K
L
M
U
V
W
X
Y
Z
Figure 4: System Control LED Display
How to Clear
Correct the condition causing the alarm
and then perform a panel reset.
Correct the condition causing the trouble and
then perform a panel reset.
Correct the condition causing alarm or
trouble and then perform a manual reset.
NOTE: If another alarm or trouble occurs, the
internal buzzer automatically resounds.
Re-enable the device or devices. The system
automatically resets.
Page 14
Enter
No
Yes
0,9 Words
A Z