10.0 System Worksheet

This option allows the number of User Level 2 passwords and the value of each password to be defined.
To select the option, press 4 from Page 2 of the commission menus.
The display then prompts the
number of User Level 2
passwords allowed.
Up to ten User Level 2 passwords can be assigned and used.
Press Yes to accept the number of passwords to proceed. Press No if the number of passwords is incorrect.
Then enter the required number using the number keys.
The display then prompts the
value of the first User Level 2
password as follows:
Press Yes to accept this value and continue on to the next password.
Press Change and then enter the new number using the number keys to assign a new code value.
Repeat for each password.
When all passwords have
been accepted or changed,
the display prompts the
period that the panel should
remain in Level 2 (without a
key being pressed) before
automatically inhibiting the
keys and returning to User
Level 1.
Press Yes to accept this value and return to the commission menu. Alternatively, change the value as
required. The default time is 5 minutes.
© 2002 Radionics
D8024/D10024A Operation and Installation Guide
Page 39
D8024/D10024A
System Worksheet
50616B