Calling Up Fault Codes From The Fault Memory (Fault History) - Viessmann VITOPEND 200 Installation And Service Instructions Manual

Gas fired combi boiler
Table of Contents

Advertisement

Troubleshooting

Calling up fault codes from the fault memory (fault history)

The 10 most recent faults are saved
and may be scanned.
The faults are ordered according to
date, thus the most recent fault is fault
number 1.
Fault codes
Display
Const.
Weath.‐
fault
comp.
code
0F
X
X
10
X
X
18
X
X
20
X
X
28
X
X
80
1. G + d press simultaneously for
2. a/b
3. Note
All saved fault codes can be
deleted with e.
4. d
System char-
Cause
acteristics
Regulated op-
Maintenance Carry out mainte-
eration
Regulates as
Outside tem-
if the outside
perature
temperature
sensor
was 0 °C
shorted out
Regulates as
Outside tem-
if the outside
perature
temperature
sensor lead
was 0 °C
broken
Regulates
System flow
without flow
temperature
temperature
sensor
sensor (low
shorted out
loss header)
Regulates
System flow
without flow
temperature
temperature
sensor lead
sensor (low
broken
loss header)
approx. 2 s
press for individual fault
codes.
Terminate the scan.
Remedy
nance. After the
maintenance, set
code "24:0".
Check the outside
temperature sen-
sor (see page 89)
Check the outside
temperature sen-
sor (see page 89)
Check the low
loss header sen-
sor (see page 91)
Check the low
loss header sen-
sor (see page 91)