Viessmann VITOPEND 200 Installation And Service Instructions Manual page 67

Gas fired combi boiler
Table of Contents

Advertisement

Code 2
(cont.)
Coding in the delivered condition
Mixer circuit
F1:0
Screed function dis-
abled (only for weather‐
compensated control
unit).
Possible change
F1:1
Screed drying function
to
adjustable in accordance
F1:5
with five optional tem-
perature/time profiles
(see page 106)
Note
Observe the screed sup-
plier's instructions.
Observe DIN 4725–2.
The report to be provided
by the heating contractor
must contain the follow-
ing heat‐up details:
&
Heat‐up data with
respective flow tem-
peratures
&
Max. flow temperature
achieved
&
Operating conditions
and outside tempera-
ture during handover.
The function continues
after power failure or
after the control unit has
been switched OFF.
Heating program "Heat-
ing and DHW" will be
started after the screed
function has been termi-
nated or if the address is
manually set to 0.
F1:6
Constant flow tempera-
to
ture 20 °C
F1:15
Coding
67