Viessmann VITOPEND 200 Installation And Service Instructions Manual page 82

Gas fired combi boiler
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Display
Const.
Weath.‐
fault
comp.
code
b4
X
X
b5
X
X
b7
X
X
bA
X
bC
X
bd
X
bE
X
bF
X
82
System char-
Cause
acteristics
Regulates as
Internal fault
if the outside
temperature
was 0 °C
Regulated op-
Internal fault
eration as per
delivered con-
dition
Burner
Boiler coding
blocked
card
Mixer "Close"
Communica-
tion fault –
extension kit
for heating
circuit M2
Regulated op-
Communica-
tion fault ‐
eration without
remote control
Vitotrol re-
mote control,
heating cir-
cuit A1
Regulated op-
Communica-
tion fault ‐
eration without
remote control
Vitotrol re-
mote control,
heating cir-
cuit M2
Regulated op-
Vitotrol re-
eration
mote control
incorrectly
encoded
Regulated op-
Incorrect
eration
LON com-
munication
module
Remedy
Replace control
unit
Replace the con-
trol unit
Plug in boiler cod-
ing card or re-
place, if faulty
Check the exten-
sion kit connec-
tions and coding;
start the exten-
sion kit
Check connec-
tions, cable/lead
and coding ad-
dress "A0"
Check connec-
tions, cable/lead
and coding ad-
dress "A0"
Check remote
control DIP switch
setting (see
page 110)
Replace the LON
communication
module