Coding
Code 2
(cont.)
Coding
Internal circula-
tion pump
20
ON
21
ON
22
ON
23
ON
Coding in the delivered condition
Boiler/burner
52:0
Without flow tempera-
ture sensor for low loss
header
Domestic hot water
56:0
Do not adjust
6d:0
Drawing‐off function
disabled
6F:100
Maximum output for
DHW heating 100 %,
defaulted by the boiler
coding card
General
76:0
Without LON communi-
cation module (only for
weather‐compensated
control units)
77:1
LON user number (only
for weather‐compen-
sated control units)
56
Heating circuit
pump
Heating circuit
without mixer
OFF
OFF
OFF
OFF
Possible change
52:1
With flow temperature
sensor for low loss head-
er (automatic recognition)
6d:1
Draw‐off function with
to
runtime 1 to 15 min.
6d:15
6F:0
Max. output during DHW
to
heating adjustable from
6F:100
min. output to 100 %
76:1
With LON communication
module (automatic recog-
nition)
77:2
LON user number, adjus-
to
table from 1 to 99:
1 ‐ 4 = Boiler
77:99
5 = Cascade
10 ‐ 98 = Vitotronic 050
99 = Vitocom
Note
Allocate each number
only once.
Heating circuit
pump
Heating circuit with
mixer
Control funct.
Control funct.
OFF
OFF