Viessmann VITOPEND 200 Installation And Service Instructions Manual page 63

Gas fired combi boiler
Table of Contents

Advertisement

Code 2
(cont.)
Coding in the delivered condition
A9:7
With pump idle time:
Heating circuit pump
"OFF" when the set
value changes through
a change in operating
mode or through a
change in the set room
temperature (only for
weather‐compensated
control units)
b0:0
With remote control:
Heating mode/reduced
mode: weather‐com-
pensated (only for
weather‐compensated
control units; change
the coding only for the
heating circuit with
mixer M2)
b2:8
With remote control unit
and for the heating cir-
cuit, heating with room
temperature hook‐up
must be encoded:
Room influence factor 8
(only for weather‐com-
pensated control units;
change the coding only
for the heating circuit
with mixer M2)
b5:0
With remote control: No
room temperature‐de-
pendent heating circuit
pump logic function
(only for weather‐com-
pensated control units;
change the coding only
for the heating circuit
with mixer M2)
Possible change
A9:0
Without pump idle time
A9:1
With pump idle time, ad-
to
justable from 1 to 15
A9:15
b0:1
Heating mode: weather‐
compensated
Reduced mode: with
room temperature hook‐
up
b0:2
Heating mode: with room
temperature hook‐up
Reduced mode: weather‐
compensated
b0:3
Heating mode/reduced
mode: with room tem-
perature hook‐up
b2:0
Without room influence
b2:1
Room influence factor
to
adjustable from 1 to 64
b2:64
b5:1
Heating circuit pump
to
logic function, see the fol-
b5:8
lowing table:
Coding
63