Troubleshooting
Fault codes
(cont.)
Display
Const.
Weath.‐
fault
comp.
code
F9
X
X
FA
X
X
FC
X
X
Fd
X
X
FE
X
X
86
System char-
Cause
acteristics
Burner control
Fan speed
unit fault
too low dur-
ing burner
start
Burner control
Fan not at
unit fault
standstill
Burner control
Modulation
unit fault
valve control
faulty
Burner
Burner con-
blocked
trol unit fault
Burner
Strong inter-
blocked
ference
(EMC) field
nearby,
faulty boiler
coding card
or main PCB
Remedy
Check the fan, fan
connecting
cables, fan power
supply and con-
trol; press "E"
Check fan, fan
connecting cables
and fan control;
press "E"
Check modulation
valve control
Check the ignition
electrodes and
connecting
cables/leads;
check whether
there are strong
fields of interfer-
ence (EMC) near
the equipment;
press "E". Re-
place the control
unit if the fault
persists
If equipment will
not restart, re-
move the EMC
field, check the
boiler coding card
and replace it or
the control unit, if
required