Mapping Input Power From Ac Power Distribution Modules To Ac Power Supply Modules On Mx2000 Routers - Juniper MX2020 Hardware Manual

Universal routing platform
Hide thumbs Also See for MX2020:
Table of Contents

Advertisement

Table 67: Calculating AC Thermal Output
Power Distribution Module
MX2020 Three-phase delta AC PDM
MX2020 Three-phase wye AC PDM
RELATED DOCUMENTATION
MX2020 Power Subsystem Description | 91
MX2020 AC Power Requirements | 167
Connecting AC Power to an MX2020 Router with Three-Phase Delta AC Power Distribution Modules
Connecting AC Power to an MX2000 Router with Three-Phase Wye AC Power Distribution Modules
MX2020 AC Power Subsystem Electrical Specifications
MX2020 AC Power Cord Specifications
MX2020 AC Power Electrical Safety Guidelines
Mapping Input Power from AC Power Distribution Modules to AC Power
Supply Modules on MX2000 Routers
You connect AC power to the router by connecting two AC power cords to each AC PDM. One feed maps
to six PSMs and the other maps to three PSMs.
and
Figure 73 on page 191
components of the PDM.
and PDM1/Input1 (MX2010 and MX2020).
AC PDM2/Input0 and PDM3/Input1 (MX2020 only).
Figure 72 on page 191
shows the mapping for the MX2020. The arrangement matches the internal
Table 68 on page 192
shows the AC PDM input mapping to AC PDM0/Input0
Table 69 on page 192
Thermal Output (BTUs per hour)
Maximum power divided by 0.91 * 3.41 = BTU/hr.
Input power = Maximum power divided by 0.91
Refer to
"MX2020 AC Power Requirements" on page 167
to calculate maximum power, which is dependent on
configuration and temperature.
Maximum power divided by 0.91 * 3.41 = BTU/hr.
Input power = Maximum power divided by 0.91
Refer to
"MX2020 AC Power Requirements" on page 167
to calculate maximum power, which is dependent on
configuration and temperature.
shows the mapping for the MX2010
shows the AC PDM input mapping to
190