Functions, monitoring, and protective functions
9.4 Monitoring and protective functions
9.4.4

Stall protection (only for vector control)

Description
If, for closed-loop speed control with encoder, the speed threshold set in p1744 for stall
detection is exceeded, then r1408.11 (speed adaptation, speed deviation) is set.
If the fault threshold value set in p1745 is exceeded when in the low speed range (less than
p1755 x (100% - p1756)), r1408.12 (motor stalled) is set.
If one of these two signals is set, then after the delay time in p2178, fault F07902 (motor
stalled) is returned.
Figure 9-28
Stall protection
Function diagram
FP 6730
FP 8012
Parameter
• r1408
• p1744
• p1745
• p1755
• p1756
• p2178
480
Vector control - Interface to Motor Module (ASM, p0300 = 1)
Messages and monitoring - Torque messages, motor blocked/stalled
CO/BO: Control status word 3
Motor model speed threshold stall detection
Motor model error threshold stall detection
Motor model changeover speed encoderless operation
Motor model changeover speed hysteresis encoderless operation
Motor stalled delay time