1.3.3 Vector Control without Encoder Feedback

Note: Complete section 1.3.1 (Volts/Hz control without encoder feedback).
P060 = 5
P100 = 3
P060 = 1
P115 = 4
Wait
Page 24
P060=5
Select "Drive Settings"
P100=3
Selects Vector Control
without Encoder Feedback
P060 = Return to Parameter Menu
If you plan to use an encoder, go to
section1.3.4, otherwise continue.
P115 = 4 No-Load Measurement
Uncoupled motor will ROTATE.
Alarm message "A080" will appear,
and a start command must be issued
within 20 seconds to perform the test,
otherwise P115 will unset.
This test will adjust the following
parameters
P103, P120
Wait for display to change back
o
to
009.
Version 1.0