Efficiency Vs. Load (Typical); Thermal Loss Vs. Load (Typical) - Toshiba 5000 Series Installation And Operation Manual

Industrial ups. 3-phase, 480vin - single phase, 120vout
Hide thumbs Also See for 5000 Series:
Table of Contents

Advertisement

11.2

Efficiency vs. Load (Typical)

UPS Load Capacity
15kVA
30kVA
50kVA
* Subject to change without notice.
11.3

Thermal Loss vs. Load (Typical)

UPS Load Capacity
15kVA
30kVA
50kVA
* Subject to change without notice.
5000 Series 3P1 Industrial UPS Installation and Operation Manual – 92973-001
TABLE 11.2: % EFFICIENCY AT VARIOUS LOADS 480V
25%
71.5%
70.1%
75.8%
TABLE 11.3: THERMAL LOSS AT VARIOUS LOADS 480V
0%
1028
2047
3412
Efficiency at Percent Full Load*
50%
75%
79.2%
82.8%
76.6%
79.6%
80.3%
83.6%
BTU/hr. Loss at Percent Full Load*
25%
50%
4,590
6,049
9,824
14,072
12,255
18,835
, 120V
*
IN
OUT
100%
84.3%
82.6%
83.1%
, 120V
*
IN
OUT
75%
100%
7,177
8,579
17,708
19,407
22,591
31,226
43

Advertisement

Table of Contents
loading