13.8

Audible Alarm Functions

An audible alarm (buzzer) will sound when the UPS is in the battery backup mode, has a fault, has low battery voltage, or is
in an overload condition. The buzzer will also beep each time an effective item is touched on the touchscreen. The following
chart shows the buzzer pattern durations for each condition. Time units are shown in seconds.
Any Fault (Intermittent buzz until fault clears)
Switch to Backup (Single five-second buzz)
Backup Operation (Intermittent buzz once every ten
seconds)
UPS Battery Shutdown Voltage
(Batt. Voltage 79% Normal)
Warnings:
BATT_OC, INV_UV, INV_OV, INV_OC, DCBUS_
OV, INV_OL, STARTERR, BATT_SD, BYP_OV,
DEVICEOH, BYP_UV, BYP_FERR, LOW_BATT,
BYPASS, INPUT_OV, INPUT_UV, PHASEROT,
ERROR, INP_FERR, BATT_OH, ASYNC, 72BOPEN,
USERWRN2, USERWRN3
Touching Effective Item on Touchscreen
The buzzer can be silenced most easily by pressing the Buzzer Silent button on the Quick Access Toolbar.
Alternatively, the buzzer can also be silenced by selecting the Settings tab, then set the Buzzer Silent parameter to Disable.
This will turn off the buzzer for the current alarm status, but the buzzer will still sound when the next Fault/Warning condition
occurs.
The buzzer can be disabled permanently by selecting the Settings tab then setting the parameter Buzzer Disable to
Disable. This will disable the alarm so that no alarm sounds for any Fault or Warning condition.
68
TABLE 13.1: AUDIBLE ALARMS
Condition
5000 Series 3P1 Industrial UPS Installation and Operation Manual – 92973-001
Audible Pattern
0.5 s
0.5 s
5.0 s
1.0 s
9.0 s
5.0 s
1.0 s
1.0 s
0.1 s