Conduit Landing Plates - Toshiba 5000 Series Installation And Operation Manual

Industrial ups. 3-phase, 480vin - single phase, 120vout
Hide thumbs Also See for 5000 Series:
Table of Contents

Advertisement

8.5

Conduit Landing Plates

Conduit landing plates are located On the Top and bottom of the UPS. Figure 8.4 through Figure 8.9 show the location
of the conduit landing plates with respect to the UPS as viewed from the top looking down.
Do not run the power and instrumentation cables through the same conduit.
3.6 (91)
19.5
(496)
FIGURE 8.4: 50/40KVA CONDUIT LANDING
PLATE DIMENSIONS - BOTTOM
28
(8 x Ø 0.63)
3 x 6
(76 x 152)
Control
Wiring
Power
Cabling
3.1
(78)
5000 Series 3P1 Industrial UPS Installation and Operation Manual – 92973-001
UPS
Cabinet
Footprint
MBS
Cabinet
Footprint
*DIMENSIONS:
in. (mm)
FIGURE 8.5: 50/40KVA CONDUIT LANDING
PLATES DIMENSIONS- TOP VIEW
25.1
(637)
(76 x 152)
Control
Wiring
Electronics
Cabinet
Top
25.1
(637)
2.2 (56)
Control
Wiring
Power
Cabling
Landing
Cabinet
27.9
Top
(709)
27.9
(709)
3 x 6