Storage/Operating Environment

6.1

Storage Environment

Observe the following when storing the UPS.
Store UPS indoors.
Maximum storage time for the UPS between powered operation cycles is three years. If the UPS has been stored
for a period exceeding 36 months, contact your factory authorized representative for guidance in starting the unit.
Temperature fluctuations should be minimized.
The optimal storage temperature range is 68 – 77 °F (20 – 25° C).
A maximum storage temperature range of -4 to 104 °F (-20 to 40 °C) should be observed.
The optimal relative humidity at the storage location should be between 50 – 60%.
Humidity must not exceed 90%.
Avoid locations where UPS may be exposed to corrosive gas.
Avoid locations with dirt and/or dust.
Item
Storage Location
Ambient Temperature
Relative Humidity
Altitude
Dust
Flammable Gas
6.2

Operating Precautions

Initial startup/commissioning of the UPS should be performed by factory authorized personnel.
1. The UPS should not be powered up until the entire operation manual has been read.
2. The voltage of the input power source must be within the rated input voltage range.
3. The input frequency must be within the rated input frequency range.
4. The UPS should not be used with a load that has a rated input that is greater than the rated output of the
5000 Series 3P1 Industrial UPS Installation and Operation Manual – 92973-001
TABLE 6.1: UPS STORAGE/OPERATING ENVIRONMENT STANDARDS
Environment standard
Indoors
Minimum storage temperature: -4 °F (-20 °C)
Maximum storage temperature: 104 °F (40 °C)
The relative humidity must be between 30% and 90% and without
condensation due to temperature changes.
This equipment is rated for installations up to 3280 ft. (1000 m)
above sea level. Consult with the factory to determine the derating
factor for installations above 3280 ft. (1000 m).
Dust must not exceed normal atmospheric levels and must not
include conductive particles, silicone or oils.
No flammable and/or explosive gas.
Hydrogen sulfide (H
Sulfurous acid gas (SO
Chlorine gas (Cl
Ammonia gas (NH
Nitrous acid gas (NO
Nitrous oxides (NOx)
Ozone (O
3
Hydrochloric acid mist (HCl) Less than or equal to 0.1 mg/m
S)
Less than or equal to 0.0001 PPM
2
)
Less than or equal to 0.05 PPM
2
)
Less than or equal to 0.002 PPM
2
)
Less than or equal to 0.1 PPM
3
)
Less than or equal to 0.02 PPM
2
Less than or equal to 0.02 PPM
)
Less than or equal to 0.002 PPM
3
17