Specifications; Table 3-1 Power Specifications; Table 3-2 Ups Module Information; Table 3-3 Ups Module Information (Packing Dimension) - Toshiba G2020 Series Installation And Operation Manual

480/480 v 500kva/750kva
Hide thumbs Also See for G2020 Series:
Table of Contents

Advertisement

3.3

SPECIFICATIONS

The UPS nameplate displays the rated kVA as well as nominal voltages and currents. The nameplate is located on the
backside of the UPS front left door.
Rated output
Power
500kVA / 500kW
750kVA / 750kW
UPS
Width
[kVA]
[in. (mm)]
500
(1,500)
750
(2,073)
G2020 Series UPS Installation and Operation Manual – 94861-004

Table 3-1 Power Specifications

Input voltage
3 phase / 3 wire
480V
480V

Table 3-2 UPS Module Information

Depth
[in. (mm)]
59.1
33.5
(850)
81.6
33.5
(850)

Table 3-3 UPS Module Information (Packing Dimension)

UPS
Width
[kVA]
[in. (mm)]
79
500
(1,990)
89
750
(2,260)

Table 3-4 UPS Module Efficiency

UPS
[kVA]
25%
500
97.9%
750
95.8%
Bypass input voltage
3 phase / 3 wire
480V
480V
Height
Net Weight
[in. (mm)]
[lbs. (kg)]
80.6
2,756
(2,047)
(1,250)
80.6
3,990
(2,047)
(1,810)
Depth
Height
[in. (mm)]
[in. (mm)]
41
88
(1,020)
(2,220)
41
88
(1,030)
(2,220)
Percent of Full Load
50%
75%
98.2%
98.0%
98.0%
97.9%
Output voltage
3 phase / 3 wire
480V
480V
Typ. Heating
Cable
at 100% load
Knockout
[kBTU/h]
BOTTOM
31.2
LEFT SIDE
BOTTOM
46.8
LEFT SIDE
Gross Weight
[lbs. (kg)]
3090
(1,400)
4,375
(1,970)
100%
97.6%
97.5%
TOP
TOP
17

Advertisement

Table of Contents
loading

Table of Contents