Efficiency Vs. Load (Typical); Thermal Loss Vs. Load (Typical) - Toshiba 5000 SERIES Installation And Operation Manual

Nema-3r 3-phase ups. industrial duty 3-phase ups
Hide thumbs Also See for 5000 SERIES:
Table of Contents

Advertisement

11.3

Efficiency vs. Load (Typical)

TABLE 11.3: % EFFICIENCY AT VARIOUS LOADS 208/120V
UPS Load Capacity
20kVA
30kVA
* Subject to change without notice.
TABLE 11.4: % EFFICIENCY AT VARIOUS LOADS WITH THREE TRANSFORMERS
UPS Load Capacity
20kVA
30kVA
* Subject to change without notice.
11.4

Thermal Loss vs. Load (Typical)

TABLE 11.5: THERMAL LOSS AT VARIOUS LOADS 208/120V
UPS Load Capacity
20kVA
30kVA
* Subject to change without notice.
TABLE 11.6: THERMAL LOSS AT VARIOUS LOADS THREE TRANSFORMERS
UPS Load Capacity
20kVA
30kVA
* Subject to change without notice.
46
(SINGLE AND DUAL CABINET MODELS)
Efficiency at Percent Full Load*
25%
76%
77%
(IN-, OUT-, ALTERNATE)*
Efficiency at Percent Full Load*
25%
72%
73%
(SINGLE AND DUAL CABINET MODELS)
BTU/hr. Loss at Percent Full Load*
0%
25%
1365
4849
1706
6880
(IN-, OUT-, ALTERNATE)*
BTU/hr. Loss at Percent Full Load*
0%
25%
1365
5971
1706
8519
5000 Series NEMA-3R 3-Phase UPS Installation and Operation Manual – 92975-000
, 208/120V
IN
50%
75%
100%
85%
88%
87%
87%
50%
75%
100%
81%
84%
83%
83%
, 208/120V
IN
50%
75%
5419
6281
6883
10,325
50%
75%
7203
8774
9435
14,152
*
OUT
89%
88%
85%
84%
*
OUT
100%
7591
12,563
100%
10,833
17,584