Appendix C – Installation Planning Guide
Installation Planning Guide for 5000 Series Industrial UPS 3-Phase
Important Notes:
1.
Maximum Current required at Primary AC Input based on full load output and maximum battery charging current.
2.
Output load conductors are to be installed in separate conduit from input conductors.
3.
Control wires and power wires are to be installed in separate conduits.
4.
Recommended AC input and output overcurrent protection based on continuous full load current per NEC.
5.
Wiring shall comply with all applicable national and local electrical codes.
6.
Grounding conductors to be sized per NEC Article 250-122. Neutral conductors to be sized per NEC Article
310.15.
Primary AC Input: 3Φ , 4-wire + ground.
AC Output: 3Φ, 4-wire + ground.
DC Input: 2-wire (Positive/Negative) + ground.
7.
Nominal battery voltage based on the use of VRLA type batteries (2.0 volts / cell nominal).
8.
Maximum battery discharge current based on lowest permissible discharge voltage of 1.6 VPC.
9.
DC Circuit Breaker size based on breakers external to Toshiba-supplied Battery System(s) or UPS(s). (Toshiba-
supplied Battery Systems come equipped with internal circuit breakers sized to meet specific operating condi-
tions)
10.
DC wires should be sized to allow not more than a 2-volt drop at maximum discharge current.
11.
Weights do not include batteries or other auxiliary equipment external to the UPS.
12.
Sizing calculations based on the following assumptions:
Not more than 6 current-carrying conductors installed in steel conduit in ambient
temperature of 30°C.
Temperature rating of copper conductors and terminals: 75°C.
Feeder distance calculations based on NEC Chapter 9, Tables 8 and 9 data, allowing for 2% AC voltage
drop.
Reference: 2014 NEC Handbook, Table 310.16.
NOTE: Consult latest edition of applicable national and local codes for possible variations.
Ratings of wires and overcurrent devices are suggested minimums. Local conditions may vary. Consult with a registered
Professional Engineer within your local area for proper size selections.
TOSHIBA
Web Site:
80
TOSHIBA
480 V Input, 1-Phase 120 V Output
INTERNATIONAL CORPORATION
SOCIAL INFRASTRUCTURE SYSTEMS GROUP
POWER ELECTRONICS DIVISION
13131 West Little York Road
Houston, TX 77041
Telephone: 855-803-7087
Fax: 713-896-5212
https://www.toshiba.com/tic/industrial/uninterruptible-power-systems
5000 Series 3P1 Industrial UPS Installation and Operation Manual – 92973-001
5000 Series UPS

Advertisement

Table of Contents
loading

Table of Contents