Toshiba 5000 Series Installation And Operation Manual page 49

Industrial ups. 3-phase, 480vin - single phase, 120vout
Hide thumbs Also See for 5000 Series:
Table of Contents

Advertisement

Code
Function
8
BATTERY DEPLETED
FAULT
9*
OVERLOAD
10
OVERLOAD PREALARM
11
BYPS.SYNCHRONOUS
12
BYPS.ASYNCHRONOUS
13
REMOTE OPE.ENABLE
14*
LOAD ON INVERTER
15*
LOAD ON BYASS
16
LOAD ON AC
17*
BATTERY OPERATION
18
INVERTER OPERATION
19
52R CLOSED
20
72B CLOSED
21
EQUALIZING CHARGE
22
OverHeat
23
Fuse Blown
*Default Output Settings
5000 Series 3P1 Industrial UPS Installation and Operation Manual – 92973-001
Description
Activated when the battery voltage drops below the Battery
Breaker Trip Voltage defined by Cmd#526 while a Battery
Shutdown warning (BATT_SD) exist during inverter operation.
A BATT_DEP fault will be indicated on the display when this
fault occurs.
Activated when an overload of 105% or more had occurred to
the system. This is the default setting on OUT6.
Activated when the load goes over 100%. This level is adjust-
able by an Authorized Toshiba Service Provider.
Activated when the inverter voltage and bypass voltage are
synchronous.
Activated when the inverter voltage and bypass voltage are
asynchronous.
Activated when any remote operation occurs (Stop/Start In-
verter, etc.)
Activated when the power is supplied from the inverter. This is
the default setting on OUT2.
Activated when the power is supplied by the bypass. This is
the default setting on OUT1.
Activated when the power is supplied from the input via the
UPS's rectifier - inverter.
Activated when the battery is supplying power to the load
following an AC power failure. This is the default setting on
OUT3.
Activated when the inverter is operating.
Activated when 52R (Input Contactor) is commanded to closed.
Activated when 72B (Battery Breaker) is closed.
Activated when the UPS is charging the batteries at the equal-
izing charge level defined by Cmd#518. Unless commanded
to float charge by using external input IN6 or Cmd#508=Float
Charge, equalizing charge will last for duration in minutes de-
fined by Cmd#532.
Activated when Device Overheat (Chopper or Inverter IGBT) or
UPS Overheat occurs.
Activated when fuse blown fault occurs
39