50/40kVA Power and Ground Cable Routing

The Input/Output bus stubs for the UPS are shown in Figure 9.2.
Route the power and ground cables as shown in Figure 9.1, below.
The Ground wiring should be routed through the MBS, Transformer, and PE (Power Electronics) Bay bulkhead penetrations,
and fastened to the Ground Bus located on the bottom front of the PE Bay.
TOP POWER
CABLE ROUTING
BOTTOM POWER
CABLE ROUTING
5000 Series 3P1 Industrial UPS Installation and Operation Manual – 92973-001
TABLE 9.2: 30KVA CONDUIT LANDING PLATES
Landing Plate Location
TABLE 9.3: 15KVA CONDUIT LANDING PLATES
Landing Plate Location
MBS
BAY
FIGURE 9.1: UPS POWER AND GROUND CABLE ROUTING
Landing Plate Dimensions W x D x Thickness
3.3 in x 7.5 in (85 mm x 190 mm) x 16 Gauge Steel
Top:
7.5 in x 14.9 in (190 mm x 378 mm) x 16 Gauge Steel
Bottom: 6.0 in x 14.1 in (152 mm x 359 mm) x 16 Gauge Steel
Landing Plate Dimensions W x D x Thickness
3.3 in x 7.5 in (85 mm x 190 mm) x 16 Gauge Steel
Top:
4.0 in x 11.0 in (102 mm x 280 mm) x 16 Gauge Steel
Bottom: 5.8 in x 24.3 in (148 mm x 618 mm) x 16 Gauge Steel
GROUND BUS
CABLE ROUTING
PORTS
MBS
BAY
GROUND
BUS
POWER
ELECTRONICS
BAY
XFMR
BAY
31