Tab: Main – RUN/STOP
The Main tab displays the UPS Mimic Diagram and Controls button.
The middle of the display contains five buttons arranged in a diagram representing the functional model of the UPS. The
lines connecting the mimic buttons represent the power flow from input to output. A thin line indicates no current flow, and
a thick or bold line indicates current flow. See the Mimic Display current Flow Indicator illustration in Figure 12.11.
No.
1
UPS Mimic Diagram
2
UPS Control – Toggles between On-Line (UPS) and bypass (BYP) modes.
3
Information Bar – Displays status, helpful hints, acronym definitions updated every two
52
1
Main Tab Components
– Displays current status of the various UPS sub-systems
(See Sections 13.2, 13.3)
Press START: UPS starts rectifier and inverter. Enables UPS and BYP options.
Press UPS:
UPS switches to On-Line mode, label changes to BYP.
Press BYP:
UPS switches to Bypass mode, label changes to UPS.
seconds.
FIGURE 12.7: MAIN TAB COMPONENTS
5000 Series 3P1 Industrial UPS Installation and Operation Manual – 92973-001