Interfaces
5.4 Status displays
LED
ERROR or L2
(SF PROFINET LED)
MAINT or L3
(SF LED)
92
Meaning
State
-
Off
Error
Red: Continuous
light
Red: Flashes quick‐
ly
(2 Hz)
Red: Flashes quick‐
ly
(5 Hz)
INIT
Red:
Flashes slowly
(0.5 Hz)
-
Off
Error
Red
Red:
Flashes slowly
(0.5 Hz)
Red: Flashes quick‐
ly
(5 Hz)
Description
SIMOTION P320-4 is working error-free.
Bus error at the PROFINET interface.
Erroneous configuration.
FAULT state
(only in combination with L1 und L3)
During the INIT process, the SF PROFINET LED is con‐
trolled by the boot loader.
The precise flashing behavior therefore cannot be de‐
termined and displayed.
In the INIT state, 0.5 Hz flashing is displayed in the SI‐
MOTION P State.
If no project has yet been loaded, 0.5 Hz flashing is also
displayed for the INIT, which, in this case, is also re‐
tained in the Running state.
SIMOTION P320-4 works error-free.
An event has occurred which needs to be acknowledged
(alarm, message, notification).
(See Diagnostics Guide)
License missing for licensed technology objects.
Carry out the licensing to correct the error.
Further information on the licensing can be found in the
SIMOTION P320-4 E / SIMOTION P320-4 S Commis‐
sioning and Hardware Installation Manual.
FAULT state
(only in combination with L1 and L2)
A fault has occurred to which the user program cannot
respond.
The following actions may be required to rectify the fault:
● Power OFF/ON
● Recommissioning
SIMOTION P320-4 E / P320-4 S
Manual, 03/2018, A5E36004933B