Technical Data For The Sitop Smart 24 V/10 A - Siemens SIMOTION P320-4 E Manual

Table of Contents

Advertisement

Technical data

9.7 Technical data for the SITOP smart 24 V/10 A

9.7
Technical data for the SITOP smart 24 V/10 A
Table 9-2
SITOP smart 24 V/10 A
Input data
Input voltage rated value
Input voltage range
Power failure bridging
Mains frequency rated value
Mains frequency range
Input current rated value
Switch-on current (at +25° C)
Recommended miniature circuit breaker
Output data
Output voltage rated value
Output voltage tolerance
Residual ripple/spikes
Output voltage adjustment range
Output current rated value
Efficiency
Electronic short-circuit protection
Ambient conditions
Ambient temperature during storage and
transport
Ambient temperature during operation
Humidity class
Degree of protection (EN 60529)
Radio suppression level (EN 55022)
Line harmonic limitation according to
EN 61000‑3‑2
EMC immunity
EMC interference emission
Safety
Safety class (IEC 536; VDE 1006 T1)
Primary/secondary galvanic isolation
142
Technical specifications for the SITOP smart 24 V / 10 A
120/230 VAC
85 to 132 VAC / 170 to 264 VAC
> 20 ms at V
= 93/187 V
in
50/60 Hz
47 ... 63 Hz
4.1/2.4 A
< 65 A
10 A, Characteristic C
24 VDC
± 3 %
< 150/240 mV
pp
22.8 to 28 VDC
10 A
(12 A up to +45° C)
Typ. 90%
Yes;
constant current approx. 1.3 × output current rated value;
for 5 seconds extra power at 1.5 × output current rated
value
-40° ... +85° C
0° ... +60° C
Climate class 3K3 according to EN 60721;
relative atmospheric humidity 5 to 95%; no condensation
IP20
Class B
No
EN 61000-6-2;
EN 61000-4-2/-3/-4/-5/-6/-11
EN 61000-6-4
Class I
SELV output voltage according to EN 60950 and
EN 50178;
transformer according to EN 61558-2-17;
overvoltage protection in the event of an internal error
U
< 60 V
a
SIMOTION P320-4 E / P320-4 S
Manual, 03/2018, A5E36004933B