Installation/mounting
6.3 Installation notes
Connecting elements
The connecting elements for each mounting position are listed in the following:
● Standard rail mounting
● Vertical mounting
Mounting positions
The following mounting positions are permitted for the SIMOTION P320-4 and are described
in detail in the following sections:
● Standard rail mounting (Page 105)
● Vertical mounting (Page 107)
110
Material
Metal,
min. 2 mm thickness
Concrete
Plasterboard,
min. 13 mm thickness
Material
Concrete
Plasterboard,
min. 13 mm thickness
Bore diameter
5 mm
6 mm, 40 mm depth
14 mm
Bore diameter
6 mm, 40 mm depth
8 mm, 40 mm depth
14 mm
Fastener
● 2 x M4 screws
● 2 x M4 nuts
● 4 x dowels, ∅ 6 mm, 40 mm length
● 4 x screws, ∅ 4 mm, 40 mm length
4 x toggle bolts, ∅ 4 mm, 50 mm length
Fastener
● 4 x dowels, ∅ 6 mm, 40 mm length
● 4 x screws, ∅ 4 mm, 40 mm length
● Dowel, ∅ 8 mm, 40 mm length
● Screw, ∅ 5 mm, 40 mm length
Toggle bolt, ∅ 4 mm, 50 mm length
SIMOTION P320-4 E / P320-4 S