Message overview
(cont.)

AA Cancel defrost

: Compressor remains off until the flow tempera-
ture in the secondary circuit has reached 15 °C.
Booster heaters are started if necessary (instan-
taneous heating water heater or external heat
generator).
:
Switch to central heating/DHW heating
Cause
Flow or return temperature in the secondary circuit
too low during defrosting
The pipework flow rate may be too low
AB Instant.htg wtr heater
Instantaneous heating water heater does not start up.
Cause
Instantaneous heating water heater faulty
High limit safety cut-out has responded.
No temperature rise within 24 h
AC compressor block
The compressor shuts down permanently in order to
prevent appliance damage.
Central heating and DHW heating is only possible
with booster heaters.
Cause
Temperature sensors in the refrigerant circuit are faul-
ty
Pressure sensor faulty
Safety high pressure switch has responded.
Electronic expansion valve faulty
Compressor drive faulty
: Fan faulty
Measure
Provide additional heating water buffer cylinder in the
secondary circuit return.
!
Please note
If the temperature in the secondary circuit is too
low, the condenser may freeze up or a thick lay-
er of ice may form on the evaporator.
Only acknowledge the fault message when the
flow temperature in the secondary circuit has
reached at least 15 °C.
Measure
Danger
Contact with live components can lead to seri-
ous injury from electric current.
Isolate the power supply prior to starting work
on the appliance.
Check power supply, connecting cable and plug for
the instantaneous heating water heater.
Check instantaneous heating water heater control
signal at terminals 211.3 (stage 1, see "Main PCB")
and 224.4 (stage 2, see "Expansion PCB").
Check high limit safety cut-out, and reset if required.
Check instantaneous heating water heater.
Measure
Calling up further heat pump messages: "Message
history"
Observe messages from the refrigerant circuit con-
troller: "Diagnosis"
"Refrigerant circuit"
sage history"
Check temperature sensors in the refrigerant circuit.
Check pressure sensor.
Check safety high pressure switch.
Check electronic expansion valve.
Check compressor drive.
Troubleshooting