Message overview
(cont.)
Cause
Short circuit, bottom cylinder temperature sensor

58 Cylinder sensor top

If only the upper cylinder temperature sensor is
present: No DHW heating
If an additional lower temperature sensor is installed:
DHW heating possible, switched on and off via this
sensor
Cause
Lead break, top cylinder temperature sensor
5A Cylinder sensor bottom
If only the lower cylinder temperature sensor is
present: No DHW heating
If an additional upper temperature sensor is installed:
DHW heating possible, switched on and off via this
sensor
Cause
Lead break, bottom cylinder temperature sensor
60 Buffer temp. sensor
For central heating:
Buffer cylinder is heated once every hour.
Heating stops when the temperature at the secon-
dary circuit return temperature sensor reaches the
set value for heating the buffer cylinder.
Cause
Short circuit, buffer temperature sensor
63 Boiler sensor ext HS
Mixer external heat generator opens fully as soon as
the external heat generator is switched on.
Frost protection monitoring of external heat genera-
tor is not active.
Measure
Check resistance value (NTC 10 k
terminals X25.7/X25.8: See "Controller and sensor
PCB".
Measure
Check resistance value (NTC 10 k
terminals X25.5/X25.6: See "Controller and sensor
PCB".
Measure
Check resistance value (NTC 10 k
terminals X25.7/X25.8: See "Controller and sensor
PCB".
For central cooling with heating water/coolant buffer
cylinder:
Heating water/coolant buffer cylinder is cooled once
every hour.
Cooling stops when the temperature at the secon-
dary circuit return temperature sensor reaches the
set value for cooling the heating water/coolant buffer
cylinder.
Measure
Check resistance value (NTC 10 k
"Controller and sensor PCB".
Troubleshooting
) at plug F7 or at
Ω
) at plug F6 or at
Ω
) at plug F7 or at
Ω
) at plug F4: See