2034 Influence room temperature hook-up cooling circuit

Only for system with heating water/coolant buffer cylin-
der ("Enable buffer cylinder/low loss header 7200"
set to "2"):
The higher the value, the greater the influence of the
room temperature on the set flow temperature of the
cooling circuit with weather-compensated control.
Conditions:
Room temperature sensor is connected, e.g. via
remote control.
2040 Cooling curve level
Only for system with heating water/coolant buffer cylin-
der ("Enable buffer cylinder/low loss header 7200"
set to "2"):
For weather-compensated central cooling via the heat-
ing/cooling circuit, the flow temperature value deter-
mined from the cooling curve is adopted directly as the
set value.
2041 Cooling curve slope
Only for system with heating water/coolant buffer cylin-
der ("Enable buffer cylinder/low loss header 7200"
set to "2"):
For weather-compensated central cooling via the heat-
ing/cooling circuit, the flow temperature value deter-
mined from the cooling curve is adopted directly as the
set value.
Parameter group Heating circuits/Cooling circuits
Example:
See "Influence room temperature hook-up 200A".
Note
Room temperature hook-up is OFF at a setting of "0".
Set value without unit
/
Setting 1
/
Setting 1
/
!
"Vitotronic 200" operating instructions
0.1 K
"Vitotronic 200" operating instructions
0.1
245