Diagnosis

Photovoltaics

PV statistics
Overview for utilisation of power generated on site:
The following information is displayed:
Exported or drawn electrical output
Heating system functions enabled and/or active for
utilisation of power generated on site
1. Service menu:
Press and hold OK +
approx. 4 s.
2. "Diagnosis"
3. "Photovoltaics"
4. "PV statistics"
Meaning of values and symbols
Display
"L1", "L2", "L3"
"Average"
"Threshold"
Heating system functions for utilisation of power generated on site:
"n.a."
Function not enabled
"
"
Function enabled but not active
–––
"Active" Function enabled and active
"Set DHW temp. 2"
"Swimming pool"
"DHW cylinder"
"Cool. room temp."
"Htg wtr buff cyl"
180
simultaneously for
å
Meaning
Excess electrical energy from the photovoltaic system is fed into the power grid.
The electrical power consumed by the heating system is taken into account (utilisa-
tion of power generated on site), with the exception of lag heat pumps in a heat
pump cascade.
Power from the grid is consumed in the building.
Consumers in the building and the heating system are not consuming electrical
energy.
or
The energy meter is faulty.
Electrical power measured by the energy meter in kW for each phase:
Positive value: Electrical power is fed into the power grid.
Negative value: Electrical power is drawn from the power grid.
Note
The polarity can be changed by a heat pump installer certified by Viessmann.
Average of electrical outputs of all 3 phases, averaged over the last 10 min
Setting value of parameter "Threshold for electrical power 7E04"
or
If "Threshold for electrical power 7E04" is set to "0": 25 % of "Compressor
output 5030"
Once a week, the DHW cylinder is fully heated with power from the photovoltaic
system to "Set DHW temperature 2 600C" ("Enable own energy consumptn for
set DHW temperature 2 7E10").
Function not available
DHW heating with utilisation of power generated on site ("Enable own energy con-
sumption for DHW heating 7E11")
Central cooling with utilisation of power generated on site ("Enable own energy
consumption for cooling 7E15")
Heating the buffer cylinder with utilisation of power generated on site ("Enable own
energy consumptn for heating water buffer cyl. 7E12")
PV statistics
L1: 4.32 kW
L2: 4.29 kW
Average:
4.35 kW
Set DHW temp. 2
n.a.
DHW cylinder
n.a.
Htg wtr buff cyl
Active
Rm temp raising
Active
Set DHW temp 2 in progress
Back with
Fig. 41
L3: 4.31 kW
Threshold:
3.0 kW
Swimming pool
---
Cool. room temp.
n.a.
Coolant buff cyl
---
Weather data
---
Yes
Remaining days:3