PCBs and connection options

Luster terminals, Vitocal 111-S/222-A/222-S

Signal and safety connections and 230 V~ compo-
nents
1/N/PE
230 V/50 Hz
N
6
7
1
L1
G
X40
N
N
N
N
N
Fig. 68
F1
Fuse 6.3 A H (slow)
X1
Terminals X1.
for earth conductors of all asso-
?
ciated system components
X2
Terminals X2.N for neutral conductors of all asso-
ciated system components
X3
Switched phase L': X3.1
Terminals for signal and safety connections and
components 230 V~
X40 Terminals for heat pump control unit power sup-
ply
Terminals
Function
X3.1
Switched phase
X3.3
Flow switch
X3.4
X3.6
Power-OFF
X3.7
G
294
8
9
3
4
1
1
1
´
X3
X2
N
N
N
N
N
N
N
X1
Explanation
Note
Observe the total load 1000 W of all connected compo-
nents.
Requires floating contact:
Closed: Heat pump operational
Open: Heat pump shut down
Breaking capacity 230 V, 0.15 A
No jumper should be installed if a flow switch is con-
nected.
Requires floating contact:
Closed: Heat pump operational
Open: Heat pump shut down
Breaking capacity 230 V, 0.15 A