Vitovent 200-C: Frost Protection - Viessmann VITOTRONIC 200 Service Instructions Manual

Heat pump control unit
Table of Contents

Advertisement

Mechanical ventilation with Vitovent 200-C/300-F
Vitovent 300-F: Conditions for passive cooling
Note
Ventilation level
is set while the bypass opens or
1
closes.
Passive cooling ON
All of the following conditions must be met:
Outdoor air temperature (heat exchanger air intake) <
extract air temperature minus 4 K
Supply air temperature > "Min. supply air tempera-
ture for bypass 7D0F" minus 1.5 K
Outdoor air temperature (heat exchanger air intake) >
"Min. supply air temperature for bypass 7D0F"
plus 1.5 K
Extract air temperature > "Set room temperature
7D08" plus 1 K
Passive cooling will not start if one of the following
conditions is met (bypass not active):
A sensor or fan fault has occurred.
Frost protection is active.
If central heating is switched on:
Central heating via one heating circuit that also sup-
plies the ventilated rooms ("Heating circuit for
blocking bypass damper 7D21").
This prevents heat supplied via the heating circuits
being routed outside via the bypass.
"Set room temperature 7D08" is set min. 4 K
higher than "Standard room temperature 2000".

Vitovent 200-C: Frost protection

Defrost functions
The degree of icing up of the heat exchanger is moni-
tored. The selected defrost function is activated
according to the degree of ice formation: See following
table.
The determine the degree of ice formation the two fol-
lowing variables are observed and additional condi-
tions are taken into account, e.g. the installation posi-
tion of the ventilation unit ("Installation position
7D2F").
Fan speeds:
The pressure differential in the heat exchanger rises
with increasing ice formation. The fan speeds are
automatically increased to maintain a constant air
flow rate. From a certain speed onwards it is
assumed that the heat exchanger is iced up.
Supply air temperature:
The heat exchanger transfers less heat from the
extract air to the outdoor air due to ice formation.
The supply air temperature drops. From a certain
supply air temperature threshold onwards it is
assumed that the heat exchanger is iced up.
(cont.)
Passive cooling OFF
One of the following conditions must be met:
Outdoor air temperature (heat exchanger air intake)
extract air temperature minus 3 K
Supply air temperature
ture for bypass 7D0F" minus 1.5 K
Outdoor air temperature (heat exchanger air intake)
"Min. supply air temperature for bypass 7D0F"
plus 1.5 K
Extract air temperature
7D08"
Monitoring of ice formation is active under the following
conditions:
The outdoor air temperature is below 2 °C.
No defrost function was active during the last 15 min.
The fans are switched on.
None of the temperature sensors in the ventilation
unit is faulty.
The defrost function is selected with the parameters
"Enable preheater bank electric 7D01" and "Strat-
egy, passive frost protection 7D2C".
Function description
"Min. supply air tempera-
"Set room temperature
61