Mechanical Ventilation With Vitovent 200-C/300-F - Viessmann VITOTRONIC 200 Service Instructions Manual

Heat pump control unit
Table of Contents

Advertisement

Function description
Mechanical ventilation
Functions
Controlled mechanical ventilation with heat recovery
Passive cooling
Passive heating
Supply air heating in conjunction with an integral hy-
draulic reheating coil (ventilation heating circuit)
Humidity and CO
concentration control
2

Mechanical ventilation with Vitovent 200-C/300-F

Controlled mechanical ventilation
The ventilation unit controls the fan speed so that a
consistent air flow rate is achieved for each ventilation
level. This means that the pressure drop of the duct-
work and filters does not affect the air flow rate.
Ventilation levels
Ventilation lev-
Function/operating pro-
el
gram
Communication interrupted
Ventilation unit switched off
"Standby mode"
0
"Economy mode"
1
"Standard operation"
"Holiday program"
"Ventilation program"
2
3
4
"Intensive operation"
Note
"Standard operation" is active automatically between
the time phases in the time program.
"Vitotronic 200" operating instructions
58
(cont.)
Operating status in
the "Time prog
ventilation"
"Reduced"
"Standard"
"Intensive"
Vitovent
200-C
200-W
300-C
X
X
X
X
X
X
Vitovent air flow rate
200-C
50 m
50 m
"Flow rate reduced ventilation 7D0A"
Factory setting:
75 m
"Flow rate nominal ventilation 7D0B"
Factory setting:
115 m
"Flow rate intensive ventilation 7D0C"
Factory setting:
155 m
"Intensive operation" is limited to "Intensive venti-
lation duration 7D1B".
Vitovent 200-C: If "Intensive operation" was activa-
ted via a switch or button (bathroom switch), the
duration is limited to "Duration, bathroom vent.
7D3B".
300-F
300-W
X
X
X
X
X
X
X
X
X
X
X
300-F
3
/h
85 m
0 m
3
/h
0 m
3
/h
85 m
3
/h
120 m
3
/h
170 m
3
/h
215 m
3
/h
3
/h
3
/h
3
/h
3
/h
3
/h