Vitodens 200-w, b2ha
models 45 to 150
wall-mounted, gas-fired condensing boiler in conjunction
with the vitotronic 300-k mw2c cascade control
for operation with natural gas and liquid propane gas
heating input 55 to 530 mbh
16 to 150 kw
read and s (20 pages)
VIESMANN Operating instructions for the system user Heating system and domestic ventilation system with heat pump control unit Vitotronic 200, type WO1C VITOTRONIC 200 Please keep safe. 5623 540 GB 8/2012...
Safety instructions For your safety Please follow these safety instructions closely to Installation conditions prevent accidents and material losses. Please note Safety instructions explained Incorrect ambient conditions can lead to system damage and can put safe operation at risk. Danger This symbol warns against the risk of injury.
Index Index 1. Introductory information Commissioning ..................Terminology ................... Your system is preset at the factory ............Energy saving tips ................. Tips for greater comfort ................. 2. About the controls Opening the control unit ................. Programming unit .................. "Operating info" ................... 10 ■...
Page 4
Index Index DHW heating outside the time program ..........28 Activating "1x DHW heating" .............. 28 ■ Stopping DHW heating ................28 6. Heating system with elec- ........................29 tric booster heater 7. Active cooling mode Enabling and blocking active cooling mode ........... 30 8.
Page 5
Index Index (cont.) "Power-OFF C5" is displayed ..............47 "Controls locked out" is displayed ............47 "Check filter" is displayed ..............47 Doors/windows can only be opened with difficulty ......... 47 Doors/windows bang when opened ............48 16. Maintenance Cleaning the heating system ..............49 In conjunction with a brine/water or water/water heat pump ....
Introductory information Commissioning The commissioning and matching up of the heat pump Note control unit to local conditions and to the structural These operating instructions also describe functions characteristics of the building, plus the instruction of that are only available on some heat pump models or the user in operating the system, must be carried out only with accessories.
Introductory information Energy saving tips Central heating/Central cooling Thermostatic valves: ■ Ensure that thermostatic valves are set correctly. Standard room temperature ("Set room tempera- Radiators: ■ ■ ture", see page 20): Never place things in front of radiators or thermo- Never overheat your home.
Page 8
Introductory information Tips for greater comfort (cont.) Heating curve/cooling curve (see page 22): ■ The heating curve enables you to individually adjust the heating system to the actual heat demand in your home. If set correctly, your preferred temperature will be achieved all year round.
About the controls Opening the control unit The heat pump control unit may look different depend- ing on the type of heat pump. Control unit at the front of the heat pump 21°C 14°C Fig. 1 Control unit on top of the heat pump Control unit mounted on the wall Fig.
About the controls Programming unit (cont.) 21 °C 14 °C Fig. 4 Takes you to the previous step in the menu or OK Confirms your selection or saves the setting. cancels a setting you have started to input. Calls up "Operating info" (see following chapter) Cursor keys or additional information on the selected menu.
About the controls Programming unit (cont.) Preheater bank for the ventilation unit is active, if Messages: installed. Symbol using fan stage 2 as an exam- Fault Warning Ventilation unit was switched off at the ON/OFF Note switch Standard menu In the standard menu, you can make and call up the How to call up the standard menu: following settings for the preferred heating/cooling cir- If the screen saver is active (see page 12):...
About the controls Extended menu In the extended menu, you can adjust and call up all Note settings from the heat pump control unit's range of Your heating contractor can block the operation of the functions, such as inputting settings for the holiday extended menu.
About the controls How to use the controls (cont.) 21 °C 14 °C Flow temperature 40 °C Menu Heating/cooling System Manual mode Continue with Heating circuit 1 Ù Ú Htg circuit selection Ù Ú Ù Ú Party mode ê Ú Economy mode ê...
Page 14
About the controls Operating program (cont.) Heating/cooling System version with DHW heating System version without DHW heating circuits Symbol Operating program Symbol Operating program Separate cooling "Standby mode" "Standby mode" circuit "Only DHW" — — "SKK" "Cooling and DHW" "Coolng" (Factory setting) Symbol Operating program...
About the controls Operating program (cont.) Operating programs for ventilation Operating program Operating status Air flow rate Ventilation stage "Standby mode" No ventilation — "Standard operation" Minimum air flow rate — "Ventilation program" "Reduced" Reduced air flow rate "Standard" Standard air flow rate "Intensive"...
About the controls Time program (cont.) The individual operating status is displayed by bars ■ of different heights on the time chart. Where several time phases overlap, the operating status with the highest bar takes priority. In the extended menu, you can call up the time pro- ■...
About the controls Time program (cont.) Setting the time program efficiently Example: You want to set the same time program for every day except Monday: 1. Select the "Monday Sunday" part of the week and – input the time program settings. Heating time program Monday-Sunday ê...
Start-up/shutdown Starting the heat pump The heat pump control unit may look different depend- ing on the type of heat pump. Control unit at the front of the heat pump 21°C 14°C Fig. 14 Fault indicator (red) ON indicator (green) ON/OFF switch Control unit on the heat pump Fig.
Start-up/shutdown Starting the heat pump (cont.) After a short time, the standard menu is displayed (see page 11) and the green ON indicator illumi- nates. Your heat pump and, if installed, your remote control units are now ready for operation. Stopping the heat pump With frost protection Select the operating program "Standby mode"...
Central heating/central cooling Room temperature Further information can be found in chapter "Terminology" in the appendix. Setting the standard room temperature for heating/cooling Factory setting: 20 °C 4. "Set room temperature" 5. Set the required value. For the priority heating/cooling circuit Note Standard menu 1.
Central heating/central cooling Time program Further information can be found in chapter "Terminology" in the appendix. Setting the time program for heating/cooling Factory setting: One time phase from 00:00 to 24:00 h Operating status for heating/cooling for every day of the week with the operating status "Standard".
Central heating/central cooling Heating system with heating water buffer… (cont.) Note "Fixd value" ■ Between the time phases, the heating water buffer The entire volume in the heating water buffer cylin- ■ cylinder is not heated; only the frost protection for the der is charged to a fixed temperature.
Central heating/central cooling Switching off central heating/central cooling For the priority heating/cooling circuit 3. If necessary, press / for the required heating/cool- ing circuit. Standard menu 4. "Operating program" 1. / for the operating program: "Only DHW" (no central heating/central cooling) ■...
Central heating/central cooling Energy saving function "Economy mode" Setting "Economy mode" for heating Extended menu Note The display of the set room temperature does not ■ 2. "Heating" or "Heating/cooling" change. 3. If necessary, / for the required heating/cooling cir- In "Economy mode", cooling via a heating/cooling ■...
Central heating/central cooling Energy saving function "Holiday program" (cont.) Central cooling: Display in the extended menu ■ No cooling via any heating/cooling circuit. A separate cooling circuit continues to be cooled. In the extended menu, you can call up the set holiday DHW heating: program under "Information"...
DHW heating DHW temperatures Setting the standard DHW temperature Factory setting: 50 °C 3. "Set DHW temperature" 4. Set the required value. Extended menu 2. "DHW" Setting the higher DHW temperature Factory setting: 60 °C Extended menu The DHW will be heated to the higher DHW tempera- 2.
DHW heating Time program (cont.) 3. "Time program DHW" Special feature with operating status "Standard" 4. Set the required time phases and operating status. and "Temp. 2" Procedure for setting a time program, see page 15. With the following system versions, the entire volume Note of the DHW cylinder is heated: Between the time phases, DHW is not heated;...
DHW heating Time program (cont.) Operating status for the DHW circulation pump "5/25 cycls" ■ The DHW circulation pump starts twice per hour for 5 min (25 min pause). "5/10 cycls" ■ The DHW circulation pump starts four times per hour for 5 min (10 min pause).
Heating system with electric booster heater Heating system with electric booster heater Note Further information can be found in chapter Constant operation of an electric booster heater results "Terminology" in the appendix. in high electricity consumption. Enabling or blocking the electric booster heater for central heating Factory setting: Locked Extended menu 2.
Active cooling mode Enabling and blocking active cooling mode Further information can be found in chapter "Terminology" in the appendix. Note The cooling function must be set by your heating ■ contractor. Constant operation of active cooling mode results in ■...
Air/water heat pumps Air/water heat pumps Setting the time program for quieter operation Further information can be found in chapter "Terminology" in the appendix. Factory setting: No time phase from 00:00 to 24:00 h for every day of the week. The fan runs at full speed (100 %) when there is a heat demand.
Ventilation Starting ventilation Display in the standard menu Further information can be found in chapter "Terminology" in the appendix. The ventilation unit is switched on by your heating con- tractor during commissioning (for the position of the 21 °C 14 °C ON/OFF switch, see chapter "Filter change"...
Ventilation Operating program (cont.) Setting the operating program for ventilation Extended menu 2. "Ventilation" 3. "Operating program" 4. For example "Ventilation program" For further possible operating programs, see page 15. Ventilation without heat recovery Further information can be found in chapter "Terminology"...
Ventilation Time program (cont.) Extended menu: "Standard" ( ■ Standard air flow rate (nominal air flow rate). 2. "Ventilation" If a humidity and/or CO sensor is installed in your 3. "Time prog ventilation" home, then the air flow rate will be adjusted accord- 4.
Ventilation Energy saving function "Economy mode" (cont.) Ending "Economy mode" Automatically on changeover to operation with mini- ■ mum air flow rate ( ) in accordance with the time program. That is, between the selected time phases. Set "Economy mode" to "OFF". ■...
Power from a photovoltaic system Own consumption of power Further information can be found in chapter "Terminology" in the appendix. Components that may be enabled for consumption Requirements of power on site DHW cylinder You would like to heat the DHW cylinder to a higher DHW heating must be switched ON (operating program ■...
Further adjustments Setting the display contrast Extended menu 3. "Contrast" 4. Set the required contrast. 2. "Settings" Setting the display brightness If you would like the texts in the menu to be more 3. "Brightness" clearly legible, change the brightness for "Control". 4.
Further adjustments Setting the preferred heating/cooling circuit for the standard menu Advanced menu 2. "Settings" 3. "Standard menu" 4. Select the heating/cooling circuit: "Heating circuit 1" (for heating circuit 1 or heat- ■ ing/cooling circuit 1) Display "HC1" "Heating circuit 2" (for heating circuit 2 or heat- ■...
Further adjustments Restoring factory settings (cont.) System setting Settings and values that are reset "System" Time program for the heating water buffer cylinder. ■ Electric booster heater is blocked for central heating. ■ Time program for electric booster heater. ■ "DHW"...
Calling up Calling up information You can call up current temperatures, set values, time Detailed call-up options for the individual groups can programs and operating states. be found in chapter "Extended menu overview" see (page 54). The extended menu splits the information into groups: "System"...
Calling up Calling up information (cont.) The central heating will operate in accordance with a Remaining duration of screed drying ■ set time program. Your settings for central heating/ central cooling have no effect for the duration of Screed drying lasts up to 32 days. The value displayed screed drying.
Calling up Calling up messages (cont.) 1. Pressing OK provides you with additional informa- Note tion regarding the displayed message. If you have connected signalling equipment for fault ■ messages (e.g. a buzzer), this will be deactivated Note when the fault message is acknowledged. Outside temp.
Manual mode Manual mode In manual mode, central heating and DHW heating operate independently of the time programs: Unregulated heating with a set flow temperature of ■ 45 °C. DHW heating with "Set DHW temperature 2" (see ■ page 26). No cooling.
Special system versions Special system versions Further information can be found in chapter "Terminology" in the appendix. The displays in the standard menu and the extended menu differ depending on the system version. At both control levels, only those functions that are rel- evant for your system version are available to you.
What to do if... Rooms are too cold Cause Remedy The heat pump is switched off. Switch the ON/OFF switch ON (see diagrams from ■ page 18). Switch ON the mains isolator (if installed, outside the ■ boiler room). Reset the MCB in the power distribution board (main ■...
What to do if... Rooms are too hot Cause Remedy Heat pump control unit set incorrectly Central heating/central cooling must be enabled. ■ Remote control (if installed) set incorrectly. ■ Check settings and correct if required: Separate operating instructions Operating program (see page 20) ■...
What to do if... " " is flashing and "Note" is displayed Cause Remedy Reference to a special event or operating state of the Proceed as described on page 41. heat pump or heating system. " " is flashing and "Warning" is displayed Cause Remedy Warning due to a specific event or operating state of...
What to do if... Doors/windows bang when opened Cause Remedy In highly airtight buildings, for example a passive Inform your local heating contractor. house: Air flow rates of your ventilation unit for supply air and extract air are out of balance.
Maintenance Cleaning the heating system In conjunction with a brine/water or water/water heat pump You may clean the appliance with a commercially available domestic cleaning agent (non-scouring). In conjunction with an air/water heat pump Please note Commercially available domestic cleaning agents and special cleaning agents for evapora- tors can damage the heat pump.
If connecting cables of the appliance or externally installed accessories are damaged, replace them with special connecting cables. Replace only with Viessmann cables. Notify your heating contractor accordingly. Cleaning the domestic ventilation system The casing of the ventilation unit may be cleaned with...
Maintenance Cleaning the domestic ventilation system (cont.) Note If required replace the filters, see next chapter. ■ Never alter the setting of annular gap ■ Replacing filters in the extract air valves Note Replace filters if one of the following conditions applies: The heat pump control unit displays "Check filters".
Page 52
Maintenance Replacing the ventilation unit filters (cont.) Remove the left or right side panel Fig. 48...
Maintenance Replacing the ventilation unit filters (cont.) Replace filter Fig. 49 Extract air filter Outdoor air filter Resetting the service display 1. Start the ventilation unit after changing the filters. Please note Dust deposits in the appliance can result in malfunctions Never start the appliance without supply air and extract air filters.
Appendix Refrigerant This heat pump contains fluorinated hydrocarbons The refrigerants used have the following global warm- (refrigerant) included in the Kyoto Protocol. ing potential: The type plate indicates the type of refrigerant used in R 134A: 1300 ■ the heat pump. R 410A: 1890 ■...
Page 55
Appendix Calling up options under "Information" (cont.) System Heating circuit 1, 2, 3 (HC1/HC2/HC3) "Outside temperature" "Operating program" "Heating and DHW" ■ "Common flow temp" "Only DHW" ■ "Operating status system" "Standby mode" ■ "Time prog. noise red." "Party mode" ■...
Appendix Terminology (cont.) At the next period of demand according to the time program the required water temperature will then ide- ally be available, i.e. the heat pump will only need to reheat a little, if at all. Electric booster heater If the required room temperature or DHW temperature Note cannot be achieved with the heat pump alone, an elec-...
Appendix Terminology (cont.) Note Weather-compensated heating mode/cooling mode In reduced heating mode, cooling is disabled. In weather-compensated mode, the flow temperature Room temperature-dependent heating mode/cool- is controlled according to the outside temperature. This ing mode means that only that amount of heat or cold is gener- ated that is actually required to heat or cool the interior In room temperature-dependent mode, a room will be to the room temperature specified by you.
Page 60
Appendix Terminology (cont.) Cooling curve Outside temperature in °C 1.4 1.6 1.8 2.0 2.2 Cooling curve slope Fig. 52 Setting the slope and level using the heating curve as an example The illustrated heating curves apply with the following settings: Heating curve level = 0 ■...
Appendix Terminology (cont.) Factory settings: Slope = 0.6 and level = 0. Outside temperature in °C Fig. 54 Changing the slope: The gradient of the heating curves changes. Changing the level: The heating curves are shifted in parallel in a verti- cal direction.
Appendix Terminology (cont.) Only one cooling circuit is possible: Example: Heating/cooling circuit "Heating circuit 1" is the heating circuit for the ■ ■ Cooling operation via one heating circuit, e.g. a room rooms occupied by you. with underfloor heating. This room can be cooled in "Heating circuit 2"...
Page 63
Appendix Terminology (cont.) Ventilation unit function Air flow To ensure that your interior suffers neither from nega- tive nor positive pressure, the air flow rate of the sup- ply air must be exactly the same as that of the extract air.
Appendix Terminology (cont.) Cooling mode See "Heating mode/cooling mode". Cooling function The natural cooling and active cooling functions are Air/water heat pumps: supported depending on the heat pump type and the "Natural cooling" ■ installed accessories. Not available. "Active cooling" ■...
Appendix Terminology (cont.) Mixer A mixer mixes the heated heating water with the When cooling via a heating circuit, e.g. an underfloor cooled water returning from the heating circuit. The heating system, the mixer serves to keep the tempera- water, heated to the right temperature in line with ture above the condensation point of the indoor air demand, is pumped to the heating circuit by the heat- (dew point).
Appendix Terminology (cont.) Compressor Central assembly of a heat pump. The compressor rai- ses the refrigerant to the temperature level required for the heating mode. Weather-compensated heating/cooling mode See "Heating mode/cooling mode". Domestic ventilation See "Controlled domestic ventilation". Time program The time programs are used to specify how your heat- For example, the operating states for central heating ing system should operate at a given time.
Page 70
Keyword index Keyword index (cont.) Operating status Reduced room temperature......... 20, 65 – DHW circulation pump..........28 Refrigerant..............54 – DHW heating............27 Remaining duration, screed drying......41 – Electric booster heater..........29 Remote control.............9 – Explanation............57, 66 Reset................38 – Heating/cooling............21 Rooms –...
Page 71
Keyword index Keyword index (cont.) Slope, heating curve/cooling curve......22 Slope/level, heating curve/cooling curve....59 Temperature Solar – Calling up..............40 – Information.............. 40 – DHW................26 – Solar energy yield........... 40 – Heating/cooling, adjusting........20 Solar circuit pump............10 – Own power consumption.........36 Solar thermal system..........
Page 72
Ventilation heating circuit........32, 63 Your contact Contact your local contractor if you have any questions regarding the maintenance and repair of your system. You may, for example, find local contractors on the internet under www.viessmann.com. Viessmann Werke GmbH&Co KG Viessmann Limited...