Option Flanges; Refrigerant Relief Valve Piping; Electrical Connection; Figure 12 - Flange For Gb Vessels - York YVAA Installation, Operation & Maintenance Instructions Manual

Air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
4" / 6" / 8" FLANGE

FIGURE 12 - FLANGE FOR GB VESSELS

Option Flanges

One of two types of flanges may be fitted depending
on the customer or local pressure vessel code require-
ments. These are Victaulic-Adapter flanges, normally
supplied loose, or weld flanges, which may be sup-
plied loose or ready-fitted. Victaulic-Adapter and weld
flange dimensions are to ISO 7005 - NP10.
WELD FLANGE
VICTAULIC ADAPTER

FIGURE 13 - FLANGE ATTACHMENT

REFRIGERANT RELIEF VALVE PIPING

The evaporator is protected against internal refrigerant
overpressure by refrigerant relief valves. A pressure re-
lief valve is mounted on each of the main refrigerant
lines connecting the evaporator to the compressors.
A piece of pipe is fitted to each valve and directed so
that when the valve is activated the release of high
pressure gas and liquid cannot be a danger or cause
injury. For indoor installations (not recommended),
pressure relief valves should be piped to the exterior
of the building.
JOHNSON CONTROLS
The size of any piping attached to a relief valve must
be of sufficient diameter so as not to cause resistance to
the operation of the valve. Unless otherwise specified
by local regulations. Internal diameter depends on the
length of pipe required and is given by the following
formula:
D
= 1.447 x L
5
Where:
• D = minimum pipe internal diameter in cm
• L = length of pipe in meters
If relief piping is common to more than one valve, its
cross-sectional area must be at least the total required
by each valve. Valve types should not be mixed on a
common pipe. Precautions should be taken to ensure
the outlets of relief valves or relief valve vent pipes
remain clear of obstructions at all times.
LD10495

ELECTRICAL CONNECTION

The following connection recommendations are in-
tended to ensure safe and satisfactory operation of the
unit. Failure to follow these recommendations could
cause harm to persons or damage the unit, and may
invalidate the warranty.
SECTION 4 - INSTALLATION
10" FLANGE
LD16185a
No additional controls (relays, and so on)
should be mounted in the control panel.
Power and control wiring not connected
to the control panel should not be run
through the control panel. If these pre-
cautions are not followed it could lead to
a risk of electrocution. In addition, elec-
trical noise could cause malfunctions or
damage the unit and its controls.
4
45

Advertisement

Table of Contents
loading

Table of Contents