FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
TABLE 7 - OPTIONAL ONE-PASS EVAPORATOR (CONT'D)
YVAA
A,B
23.3
252.5
39
8
(592)
(6414)
22.5
164.6
41
3
(572)
(4181)
22.5
252.6
42
5
(572)
(6416)
23.3
296.5
42
8
(592)
(7531)
22.3
287.1
44
3
(566)
(7292)
23.3
308.4
47
5
(592)
(7833)
22.3
331.2
48
3
(566)
(8412)
22.5
176.5
49
0
(571)
(4482)
23.3
176.2
50
0
(592)
(4475)
23.3
308.4
52
3
(592)
(7833)
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permitted. Glycol limits are higher. Please contact your Johnson Controls Sales Office for ratings and further information.
JOHNSON CONTROLS
ALL DIMENSIONS - INCHES (MM)
E-NOZZLE
C
D
SIZE
83.5
10
(2121)
83.8
10
(2129)
83.8
10
(2129)
83.5
10
(2121)
94.2
10
(2393)
71.5
10
(1816)
94.2
10
(2393)
71.7
10
(1820)
71.5
10
(1816)
71.5
10
(1816)
MINIMUM
WATER
CHILLED
VOLUME.
WATER FLOW
GALLONS
RATE
(LITERS)
GPM (L/S)
147
1090
(556)
(69)
130
940
(492)
(59)
130
940
(492)
(59)
147
1090
(556)
(69)
96
840
(363)
(53)
147
1090
(556)
(69)
96
840
(363)
(53)
130
940
(492)
(59)
147
1090
(556)
(69)
147
1090
(556)
(69)
SECTION 5 - TECHNICAL DATA
MAXIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
3420
(215)
3420
(215)
3420
(215)
3420
(215)
3320
(209)
3420
(215)
3320
(209)
3420
(215)
3420
(215)
3420
(215)
73