Vibration Isolation - York YVAA Installation, Operation & Maintenance Instructions Manual

Air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
Circuit Breaker – A unit-mounted circuit breaker with
external lockable handle will be supplied to isolate the
single point power voltage for servicing. The circuit
breaker is sized to provide motor branch circuit protec-
tion, short circuit protection and ground fault protec-
tion for the motor branch-circuit conductors, the motor
control apparatus and the motors.
Non-Fused Disconnect Switch – Unit-mounted dis-
connect switch with external lockable handle can be
supplied to isolate the unit power voltage for servicing.
Separate external fusing must be supplied by the power
wiring, which must comply with local codes.
JOHNSON CONTROLS
SECTION 2 - PRODUCT DESCRIPTION

Vibration Isolation

Elastomeric Isolation – This option is recommended
for normal installations. It provides very good perfor-
mance in most applications for the least cost. Field
mounted.
25 mm (1") Spring Isolators – Spring and cage type
isolators for mounting under the unit base rails are
available to support unit. They are level adjustable.
25 mm (1") nominal deflection may vary slightly by
application. Field mounted.
50 mm (2") Restrained Spring Isolators – Restrained
Spring-Flex Mounting isolators incorporate a rugged
welded steel housing with vertical and horizontal limit
stops. Housings designed to withstand a minimum 1.0g
accelerated force in all directions up to 51 mm (2").
The deflection may vary slightly by application. They
are level adjustable. Field mounted.