SECTION 9 - MAINTENANCE
TABLE 32 - PRESSURE TRANSDUCER OUTPUT VOLTAGE (MEASURED SIGNAL TO RETURN AT THE
TRANSDUCER)
SUCTION PRESSURE TRANSDUCER
(125 PSIG)
PRESSURE
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
172
DISCHARGE CONDENSER LIQUID PRESSURE AND
VOLTAGE
0.50
0.66
0.82
0.98
1.14
1.30
1.46
1.62
1.78
1.94
2.10
2.26
2.42
2.58
2.74
2.90
3.06
3.22
3.38
3.54
3.70
3.86
4.02
4.18
4.34
4.50
DISCHARGE PRESSURE TRANSDUCER
(400 PSIG)
PRESSURE
0
25
50
75
100
125
150
175
200
225
250
275
300
325
350
375
400
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
VOLTAGE
0.50
0.75
1.00
1.25
1.50
1.75
2.00
2.25
2.50
2.75
3.00
3.25
3.50
3.75
4.00
4.25
4.50