Table 4 - Electrical Lug Data - York YVAA Installation, Operation & Maintenance Instructions Manual

Air-cooled screw liquid chillers with variable speed drive
Table of Contents

Advertisement

SECTION 4 - INSTALLATION

TABLE 4 - ELECTRICAL LUG DATA

FIELD WIRING LUGS
YVAA MODEL
INPUT
VOLTS
FRAME COND EVAP
015
3
B
016
5
B
017
8
C
018
3
A
019
5
A
019
8
B
020
0
C
021
3
A
021
5
C
52
TERMINAL
BLOCK
WIRES
INPUT
PER
FREQ
PHASE
SINGLE POINT WIRING
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
380
60
2
#2 - 600 kcmil
400
50
2
#2 - 600 kcmil
460
60
2
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
380
60
2
#2 - 600 kcmil
400
50
2
#2 - 600 kcmil
460
60
2
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
380
60
2
#2 - 600 kcmil
400
50
2
#2 - 600 kcmil
460
60
2
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
380
60
2
#2 - 600 kcmil
400
50
2
#2 - 600 kcmil
460
60
2
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
380
60
2
#2 - 600 kcmil
400
50
2
#2 - 600 kcmil
460
60
2
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
380
60
2
#2 - 600 kcmil
400
50
2
#2 - 600 kcmil
460
60
2
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
380
60
3
#2 - 600 kcmil
400
50
3
#2 - 600 kcmil
460
60
2
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
380
60
2
#2 - 600 kcmil
400
50
2
#2 - 600 kcmil
460
60
2
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
200
60
4
#2 - 600 kcmil
230
60
4
#2 - 600 kcmil
380
60
2
#2 - 600 kcmil
400
50
2
#2 - 600 kcmil
460
60
2
#2 - 600 kcmil
575
60
2
#2 - 600 kcmil
STANDARD & ULTRA QUIET CONDENSER FANS
CIRCUIT
BREAKER
LUG
WIRES
WIRE
PER
RANGE
PHASE
4
4/0 ~ 500 kcmil
2
#2/0 ~ 500 kcmil
2
#2/0 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
4
4/0 ~ 500 kcmil
2
#2/0 ~ 500 kcmil
2
#2/0 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
4
4/0 ~ 500 kcmil
2
#2/0 ~ 500 kcmil
2
#2/0 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
4
4/0 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
4
4/0 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
4
4/0 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
4
4/0 ~ 500 kcmil
3
3/0 ~ 400 kcmil
3
3/0 ~ 400 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
4
4/0 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
4
4/0 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
2
#1 ~ 500 kcmil
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
NON-FUSED
DISCONNECT SWITCH
LUG
WIRES
WIRE
PER
RANGE
PHASE
2
#2 - 600 kcmil
2
#2 - 600 kcmil
2
#2 - 600 kcmil
2
#2 ~ 600 kcmil
2
#2 - 600 kcmil
2
#2 - 600 kcmil
2
#2 - 600 kcmil
2
#2 ~ 600 kcmil
2
#2 - 600 kcmil
2
#2 - 600 kcmil
2
#2 - 600 kcmil
2
#2 ~ 600 kcmil
3
#2 ~ 600 kcmil
3
#2 ~ 600 kcmil
2
#2 - 600 kcmil
2
#2 ~ 600 kcmil
3
#2 ~ 600 kcmil
3
#2 ~ 600 kcmil
2
#2 - 600 kcmil
2
#2 ~ 600 kcmil
3
#2 ~ 600 kcmil
3
#2 ~ 600 kcmil
2
#2 - 600 kcmil
2
#2 ~ 600 kcmil
3
#2 ~ 600 kcmil
3
#2 ~ 600 kcmil
3
#2 - 600 kcmil
2
#2 ~ 600 kcmil
3
#2 ~ 600 kcmil
3
#2 ~ 600 kcmil
2
#2 - 600 kcmil
2
#2 ~ 600 kcmil
3
#2 ~ 600 kcmil
3
#2 ~ 600 kcmil
2
#2 - 600 kcmil
2
#2 ~ 600 kcmil
JOHNSON CONTROLS